AC Motor Diagram: Stator Windings, Star-Delta Starting, and Control Circuits

Ac Motor Diagram — circuit diagram showing component connectionsBreaker 20AOn/Off SwitchOverload F1M1~Motor 1-PhaseRun Cap 25μF230V AC UtilitySingle-Phase Motor WiringRun capacitor across windings
AC Motor Diagram: Stator Windings, Star-Delta Starting, and Control Circuits — interactive diagram. Open it in the editor to customise components and wiring.

This is a free printable ac motor diagram: download the diagram as SVG or open it and print to paper or PDF.

An AC motor diagram shows the stator winding terminals, the power supply connections, and the control circuit elements — including star-delta starters and overload relays — needed to run an AC motor safely.

An AC motor is an electric motor driven by alternating current. The vast majority of AC motors in industrial, commercial, and domestic applications are induction motors — specifically squirrel-cage induction motors — because they are robust, require no brushes or commutators, and need minimal maintenance.

AC motor diagrams typically show two interconnected circuits:

1. The power circuit: The three-phase (or single-phase) supply, the main isolator, fuses or circuit breaker, the contactor (main switching device), overload relay, and the six winding terminals of the motor stator (U1, V1, W1 on one end and U2, V2, W2 on the other — per IEC 60034 designation).

2. The control circuit: Operates at a lower voltage (typically 110 V AC or 24 V DC via a control transformer). Contains the start and stop pushbuttons, the auxiliary contacts of the main contactor, the overload relay contact (normally closed), and any additional interlocks (emergency stop, thermistor relay).

The most common starting method for three-phase squirrel-cage induction motors above approximately 5.5 kW is star-delta (wye-delta) starting. In star connection (Y), the motor's winding end terminals (U2, V2, W2) are shorted together. This applies a reduced voltage of 1/√3 of the line voltage across each winding, reducing starting current to approximately 33% of the direct-on-line (DOL) starting current. After a preset time (typically 5–10 seconds), the control circuit opens the star contactor and closes the delta contactor, connecting each winding across full line voltage.

For motors below approximately 5.5 kW, direct-on-line (DOL) starting is standard. The motor connects directly to the full supply voltage through one contactor.

Single-phase AC motors use a different starting arrangement, described separately in single-phase induction motor diagrams.

All AC motor installations must comply with IEC 60364, NEC/NFPA 70 Article 430, BS 7671, or AS/NZS 3000, and must be designed and installed by qualified professionals.

AC motors cover a wide range of types, from simple single-phase induction motors to reversible and multi-speed three-phase units. An AC swing motor wiring diagram — used in ceiling fans and some oscillating appliances — typically shows a shaded-pole or PSC motor with a capacitor controlling the swing mechanism. A reversible AC motor adds an external switch or contactor that swaps the start-winding lead polarity to change rotation direction. You can map any of these configurations free in the browser-based circuit diagram editor.

How to wire ac motor diagram

  1. Identify the motor's nameplate data Record the supply voltage, frequency, full-load current (FLC), power (kW or hp), speed (RPM), insulation class, enclosure rating (IP class), starting method specified, and winding connection (delta or star at full voltage). These determine starter sizing, cable selection, overload relay setting, and protection device rating.
  2. Select the starting method For motors up to approximately 5.5 kW on a well-provisioned supply, DOL starting is typical. Above 5.5 kW, or where the supply authority or driven load restricts starting current, star-delta or electronic soft-start is required. The motor must have all six winding terminals accessible for star-delta starting — motors with only three terminals pre-connected internally cannot be star-delta started.
  3. Size the power circuit components Select the main contactor based on the motor's FLC and the AC utilisation category (AC-3 for squirrel-cage induction motors). Size the overload relay to the motor's FLC value — typically set to 0.9–1.0 × FLC. For star-delta starters, the star and delta contactors carry different currents (star contactor carries approximately 58% of line current; delta contactor carries 58% of FLC). Size the supply cable based on FLC with appropriate derating factors.
  4. Draw or read the power circuit diagram The power circuit shows: supply terminals L1, L2, L3 — main isolator — MCB or fuses — main contactor (KM1) — overload relay (OL1) — motor terminals U1, V1, W1. For star-delta, add the star contactor (KM-Y, connecting U2, V2, W2 together) and the delta contactor (KM-D, connecting U2 to V1, V2 to W1, W2 to U1). The star and delta contactors must be interlocked.
  5. Draw or read the control circuit diagram The control circuit (typically at 110 V AC or 24 V DC via a control transformer) shows: supply — emergency stop (normally closed) — stop pushbutton (normally closed) — start pushbutton (normally open in parallel with KM1 auxiliary contact for self-hold) — overload relay normally-closed contact — coil of main contactor KM1. For star-delta, add the star contactor coil, timer contact, and delta contactor coil with interlocking.
  6. Connect the motor terminal board For DOL delta connection at full voltage: bridge U1 to W2, V1 to U2, W1 to V2 using link bars on the terminal board. Connect supply phases L1, L2, L3 to U1, V1, W1 respectively. For star-delta operation, do not fit any link bars — leave all six terminals accessible for the starter's delta contactor connections.
  7. Commission and test Before first start: perform insulation resistance test (minimum 1 MΩ at 500 V DC between each winding and earth). Check direction of rotation by momentarily energising and observing the cooling fan or shaft rotation. For star-delta: check that the transition from star to delta is smooth at the timer setpoint. Measure and record running current in all three phases — they should be balanced to within 5%.

Specifications

Supply voltage (three-phase)400 V AC (Europe/IEC), 415 V AC (UK/Australia), 460–480 V AC (USA)
Supply frequency50 Hz (IEC regions); 60 Hz (USA/Canada)
Motor terminal designations (IEC 60034)U1, V1, W1 (start of windings); U2, V2, W2 (end of windings)
DOL starting currentTypically 6–7 × motor full-load current
Star-delta starting currentApproximately 33% of DOL starting current (2–2.3 × FLC)
Contactor utilisation category (squirrel-cage induction motor)AC-3 (per IEC 60947-4-1)
Motor winding insulation test (Megger)Minimum 1 MΩ at 500 V DC (IEC 60034-27)
Applicable standardsIEC 60034, IEC 60364, IEC 60947-4-1, NEC/NFPA 70 Article 430, BS 7671, AS/NZS 1359

Safety warnings

Tools needed

Common mistakes

Troubleshooting

Motor trips overload relay shortly after starting
Cause: Star-delta transition timer is set too short — motor is still at low speed and drawing high current when it switches to delta, causing the overload relay to trip Fix: Increase the transition time setpoint by 2–3 seconds and re-test. Monitor starting current with a clamp meter. The current should drop to near running current before the timer triggers the star-to-delta changeover.
Motor runs but draws unbalanced current on the three phases
Cause: One winding terminal is loose or not making full contact, a phase conductor has high resistance due to a poor crimp, or one stator winding has a partially open-circuit turn fault Fix: Isolate and LOTO. Perform an insulation resistance test and a winding resistance test on all three windings. Compare resistance values — they should be equal within 5%. Re-terminate any loose connections. If winding resistance is unequal, the motor requires rewinding.
Motor starts in star but fails to transition to delta — trips immediately on transition
Cause: Delta contactor contacts are worn or the interlock preventing simultaneous star and delta operation is failing, causing an arc or transient fault at the moment of transition Fix: Isolate and LOTO. Inspect delta contactor contacts for wear or erosion. Verify the electrical and mechanical interlock between the star and delta contactors. Replace worn contacts or the contactor assembly.
Control circuit does not respond to the start button
Cause: Overload relay has tripped and needs manual reset, or emergency stop is latched, or a control circuit conductor is open-circuit Fix: First check that the overload relay has been reset (press the RESET button on the overload relay body). Check that the emergency stop button is not latched. Use a multimeter to trace continuity through the control circuit from the supply to the contactor coil terminal.

Frequently asked questions

What do the terminals U1, V1, W1, U2, V2, W2 mean on an AC motor?

These are the standardised IEC 60034 designations for the six ends of a three-phase motor's three stator windings. U1-U2 are the two ends of winding U; V1-V2 are the ends of winding V; W1-W2 are the ends of winding W. In delta connection, U1 connects to W2, V1 to U2, and W1 to V2. In star, U2, V2, and W2 are all connected together (the star point).

What is star-delta starting and why is it used?

Star-delta starting reduces the voltage applied to each motor winding during starting by connecting the windings in star (Y). This reduces starting current to approximately 33% of DOL current, lowering mechanical shock to the driven machine and reducing voltage dips on the supply network. After the motor accelerates, it switches to delta (full voltage) connection. It is used for squirrel-cage induction motors where the load torque at starting is low.

What does the overload relay do in an AC motor circuit?

The thermal or electronic overload relay monitors the current drawn by the motor and opens its normally-closed contact in the control circuit if the current exceeds the motor's full-load rating for a sustained period. This de-energises the main contactor, disconnecting the motor from supply. It protects the stator windings from overheating — a sustained 20% overload can halve motor insulation life within hours.

How do you reverse a three-phase AC induction motor?

Reverse any two of the three phase supply conductors (L1, L2, L3) at the motor terminals. Swapping two phases reverses the direction of the rotating magnetic field in the stator, which reverses the rotor's direction of rotation. A reversing starter achieves this by using two contactors — forward and reverse — with mechanical and electrical interlocks to prevent both from closing simultaneously.

What is the difference between a DOL starter and a star-delta starter?

A DOL (direct-on-line) starter connects the motor directly to full supply voltage via a single contactor, producing full starting torque and starting current (typically 6–7 × full-load current). A star-delta starter uses three contactors and a timer to first connect in star (reduced current and torque) then switch to delta (full voltage). DOL is simpler and cheaper; star-delta is used where high starting current would cause problems on the supply or driven machine.

What does an AC swing motor wiring diagram show?

An AC swing motor wiring diagram shows a small single-phase motor (often shaded-pole or PSC type) wired to a cam-and-gear oscillating mechanism; the motor itself has a live, neutral, and sometimes a capacitor terminal. The wiring is straightforward: supply live and neutral connect to the motor terminals, with the run capacitor wired in series with the auxiliary winding if a PSC type is used. The swing motor may share the same supply as the main fan motor, switched together.

How is a reversible AC motor wired?

A reversible single-phase AC motor changes direction by swapping the connection of the start or auxiliary winding relative to the main winding. In practice this is done with a DPDT switch or a pair of contactors that interchange two of the motor leads. Three-phase AC motors are reversed simply by swapping any two of the three supply phases (T1, T2, T3) at the motor terminals or at the contactor.

Related diagrams

Free electrical calculators

Edit this diagram free in the online editor