Wire Gauge Amp Chart (NEC Table 310.16) — Copper & Aluminum Ampacity

A 12 AWG copper wire is rated for 20 A, 10 AWG for 30 A, and 8 AWG for 40 A at 60 °C per NEC Table 310.16. The full chart below lists allowable ampacities for copper and aluminum conductors from 14 AWG to 500 kcmil at 60 °C, 75 °C, and 90 °C insulation temperature ratings, followed by the ambient-temperature correction factors and conductor-bundling adjustment factors needed to derate correctly. The calculator above applies all of these tables automatically.

NEC 2023 Table 310.16 — Allowable Conductor Ampacities

Conditions of use for this table: insulated conductors rated up to 2,000 V, no more than three current-carrying conductors in a raceway, cable, or directly buried, at a 30 °C (86 °F) ambient temperature. Source: NEC 2023 Table 310.16.

Wire size (AWG / kcmil) Copper — Ampacity (A) Aluminum — Ampacity (A)
60 °C (TW, UF) 75 °C (THWN, XHHW) 90 °C (THHN, THWN-2, XHHW-2) 60 °C 75 °C 90 °C
14 AWG152025
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350

NEC Table 310.16 continues beyond 500 kcmil (600, 700, 750, 800, 900, 1000, 1250, 1500, 1750, and 2000 kcmil); the sizes above cover residential and light-commercial work. Aluminum conductors smaller than 12 AWG are not listed in the table.

Ampacity by wire size — quick facts

Which temperature column do I use?

Use the column that matches the lowest temperature rating in the circuit — usually the terminations, not the wire insulation (NEC 110.14(C)):

Ambient-temperature correction factors (NEC 310.15(B)(1))

Table 310.16 assumes a 30 °C (86 °F) ambient. For other ambient temperatures, multiply the table ampacity by the factor below (NEC 2023 Table 310.15(B)(1)(1)):

Ambient temperature (°C) Factor — 60 °C conductors Factor — 75 °C conductors Factor — 90 °C conductors
10 or less1.291.201.15
11–151.221.151.12
16–201.151.111.08
21–251.081.051.04
26–301.001.001.00
31–350.910.940.96
36–400.820.880.91
41–450.710.820.87
46–500.580.750.82
51–550.410.670.76
56–600.580.71

More than three current-carrying conductors (NEC 310.15(C)(1))

When more than three current-carrying conductors are bundled in the same raceway or cable, multiply the ampacity by the adjustment factor below:

Current-carrying conductors Adjustment factor (% of Table 310.16 ampacity)
4–680%
7–970%
10–2050%
21–3045%
31–4040%
41 and above35%

Copper vs aluminum

Aluminum has roughly 61% of copper's conductivity, so an aluminum conductor must typically be two AWG sizes larger to carry the same current: where 12 AWG copper carries 20 A at 60 °C, you need 10 AWG aluminum (25 A at 60 °C) for the same 20 A circuit. Aluminum is common for large feeders and service entrances (4/0 AWG aluminum at 75 °C is rated 180 A) where its lower cost and weight outweigh the larger size; branch circuits are almost always copper.

Common circuits — quick reference

Breaker size (A) Minimum copper wire (60 °C basis) Typical uses
15 A14 AWGLighting circuits, general receptacles
20 A12 AWGKitchen, bathroom, and garage receptacles
30 A10 AWGElectric dryer, water heater
40 A8 AWGElectric range, heat pump
50 A6 AWGRange, hot tub, EV charger (40 A continuous)
60 A4 AWGSubpanel feeder, large EV charger (48 A continuous)

Remember that 14, 12, and 10 AWG copper are capped at 15 A, 20 A, and 30 A overcurrent protection respectively regardless of the table column (NEC 240.4(D)), and long runs may need a larger conductor for voltage drop even when the ampacity is sufficient.

Last verified against NEC 2023 Table 310.16, Table 310.15(B)(1)(1), and Table 310.15(C)(1). Results are for planning; always confirm with the current NEC edition and your local authority having jurisdiction.