Connected Electrical Load Calculator — Free VA Total

Electrical lab bench with calculator, multimeter, oscilloscope, and low-voltage test circuit used to verify Electrical Load Calculator results.
Calculate the nominal result, then verify assumptions, limits, and real behavior with appropriate measurements.
Electrical Load Calculator formula, inputs, result, verification, or design-boundary visual 1 of 8
Electrical Load Calculator input-to-result overview.
Electrical Load Calculator formula, inputs, result, verification, or design-boundary visual 2 of 8
Formula and unit relationship.
Electrical Load Calculator formula, inputs, result, verification, or design-boundary visual 3 of 8
Worked-example calculation path.
Electrical Load Calculator formula, inputs, result, verification, or design-boundary visual 4 of 8
Input and assumption checklist.
Electrical Load Calculator formula, inputs, result, verification, or design-boundary visual 5 of 8
Nominal result and interpretation.
Electrical Load Calculator formula, inputs, result, verification, or design-boundary visual 6 of 8
Tolerance and worst-case verification.
Electrical Load Calculator formula, inputs, result, verification, or design-boundary visual 7 of 8
Editable-circuit and related-tool next step.
Electrical Load Calculator formula, inputs, result, verification, or design-boundary visual 8 of 8
Safety, model, and professional-review boundary.

Electrical load calculation workflow

An electrical load calculation turns an inventory of real loads into a documented design basis. Connected load is not automatically the same as demand load, service size, feeder current, energy use, or protective-device rating. The governing method depends on occupancy, load category, phase arrangement, utilization, demand/diversity rules, continuous operation, motors, heating/cooling, nonlinear loads, and local requirements.

QuantityFormulaUse
Single-phase apparent currentI = VA ÷ VConvert apparent load to nominal line current.
Three-phase apparent currentI = VA ÷ (√3 × VLL)Balanced line-current estimate from line-to-line voltage.
Real powerP = V × I × PF, or √3 × VLL × I × PFRelate watts, current, voltage, and power factor.
EnergykWh = kW × hoursEstimate consumption; not conductor or breaker size.

Worked planning example

A balanced 18 kVA three-phase load at 400 V has a nominal current of 18,000 ÷ (√3 × 400) ≈ 26.0 A. If 18 kW were entered instead of 18 kVA, power factor and efficiency assumptions would be needed before current could be estimated. The release calculation must also address phase imbalance, continuous operation, harmonics, motors, demand rules, and the selected equipment.

Build a traceable load schedule

  1. List each load with tag, description, phase, voltage, poles, watts or VA, power factor, duty, and source.
  2. Normalize units without losing the source value.
  3. Apply only the demand or diversity method permitted for the project.
  4. Summarize per phase and flag imbalance or missing data.
  5. Carry the reviewed result into the panel schedule, feeder calculation, and release package.

What this result does not prove

The calculator does not establish code compliance, protective-device coordination, available fault current, voltage drop, conductor derating, harmonic heating, generator performance, transformer inrush, or equipment suitability. Verify the governing rules through the applicable authority and current primary sources such as NFPA 70 through NFPA LiNK.