Air Circuit Breaker (ACB) Diagram: How They Work and How to Wire Them

Air Circuit Breaker Diagram — circuit diagram showing component connectionsMain Breaker 60AFuse 1 - 15AFuse 2 - 20AFuse 3 - 15AKitchen CircuitLighting CircuitBedroom Circuit230V AC UtilityFuse Box / Fuse Panel Wiring
Air Circuit Breaker (ACB) Diagram: How They Work and How to Wire Them — interactive diagram. Open it in the editor to customise components and wiring.

This is a free printable air circuit breaker diagram: download the diagram as SVG or open it and print to paper or PDF.

An air circuit breaker (ACB) is a high-current protection and switching device that interrupts fault currents using the cooling and quenching effect of atmospheric air, used for main incomer and bus protection in low-voltage distribution systems.

An air circuit breaker (ACB) is the primary overcurrent protection and switching device in large low-voltage (LV) distribution systems, typically found in main distribution boards (MDBs), motor control centres (MCCs), and industrial switchgear panels. ACBs are rated from 800 A to 6 300 A and above, handling the fault currents at the head of an installation where moulded-case circuit breakers (MCCBs) are too small.

HOW AN ACB INTERRUPTS FAULT CURRENT: When a fault current flows, it exceeds the ACB's trip threshold. The overload or short-circuit release mechanism causes the main contacts to part. At low voltage, parting contacts under fault current produce an arc. The ACB uses an arc-chute — a series of metallic arc splitter plates — to elongate, split, and cool the arc into multiple shorter arcs in series, raising the arc voltage above the supply voltage. This extinguishes the arc within the arc chamber, which is open to atmosphere (hence 'air' circuit breaker). This contrasts with a vacuum circuit breaker (VCB) or SF₆ breaker, which uses other arc-quenching media.

COMPONENTS OF AN ACB: - Main contacts (fixed and moving) — carry load current - Arc chutes (arc splitter plates) — quench the arc on opening - Overcurrent trip releases: thermal-magnetic or electronic trip unit (ETU/microprocessor-based) - Closing mechanism: stored energy spring mechanism, charged manually or by motor - Operating mechanism: includes Open (O) and Close (I) pushbuttons, or remote motor-driven operation - Auxiliary contacts: NO and NC contacts for signalling to PLCs, BCUs, or annunciators - Undervoltage release (UVR): trips the breaker if supply voltage falls below threshold - Shunt trip: trips the breaker remotely via a 24 V or 110 V DC/AC coil signal

WIRING AN ACB: The main (power) circuit: heavy busbars or cables connect at the incoming and outgoing terminals. Torque values are critical — under-torquing causes resistive heating; over-torquing crushes conductors. The control circuit: the closing coil (if motor-operated), shunt trip coil, UVR coil, and auxiliary contacts all wire into the switchgear control circuit on much smaller wires (typically 2.5 mm²). Auxiliary contacts provide breaker status (Open/Closed/Tripped) to the SCADA, BMS, or indicator panel.

ELECTRONIC TRIP UNITS (ETU): Modern ACBs use a microprocessor-based ETU with adjustable settings for long-time delay (overload), short-time delay (selective coordination), and instantaneous (short-circuit) protection. Current transformers (CTs) inside the ACB measure current on all three phases and neutral.

How to wire air circuit breaker diagram

  1. Isolate and verify dead the incoming supply ACBs handle the main incomer or bus — the supply upstream must be isolated and locked out before any work. Apply LOTO procedures. Confirm all three phases and neutral are dead using a suitably rated voltage tester before touching any terminal.
  2. Verify the ACB rating against the installation requirements Confirm the ACB's rated current (In), short-circuit breaking capacity (Icu/Ics in kA), and voltage rating match the installation requirements. The breaking capacity must exceed the prospective short-circuit current (PSCC) at the installation point.
  3. Connect the main (power) circuit conductors Connect incoming busbars or cables to the LINE terminals and outgoing busbars or cables to the LOAD terminals. Use the torque values specified on the ACB nameplate or in the manufacturer's installation manual. Under-torque causes heating; over-torque damages terminals.
  4. Wire the control circuit to the ACB auxiliary terminals Connect the shunt trip coil, closing coil, UVR coil, and auxiliary contacts as shown in the switchgear control circuit diagram. Use the ACB's internal wiring diagram (typically on the inside of the ACB cover) alongside the panel wiring diagram. Use ferrule-labelled wires for every control circuit connection.
  5. Set the electronic trip unit parameters Configure the ETU long-time pickup (overload threshold, typically 0.6 × In to 1.0 × In), long-time delay, short-time pickup and delay, and instantaneous pickup settings. Settings must be calculated as part of the protection coordination study — do not set arbitrarily.
  6. Conduct pre-commissioning checks Inspect all connections, confirm arc chutes are correctly seated, verify the operating mechanism spring charges correctly (manual or motor), and confirm the breaker racking mechanism moves freely through all positions. Check all auxiliary contacts with a continuity tester.
  7. Commission and test the protection settings Apply supply voltage and perform a secondary injection test on the ETU using a protection relay test set to verify trip times match calculated settings. Test shunt trip, UVR operation, and auxiliary contact changeover. Record all test results.

Specifications

Voltage rating (LV application)Up to 1 000 V AC (typically 415 V or 690 V AC, 50/60 Hz)
Current range (typical ACB)800 A to 6 300 A
Short-circuit breaking capacity (Icu)25 kA, 50 kA, 65 kA, 85 kA, 100 kA (depends on model)
Number of poles3-pole (three-phase) or 4-pole (three-phase + neutral)
ETU protection functions (typical)Long-time (overload), Short-time (selective), Instantaneous, Ground fault (earth fault)
Applicable standardIEC 60947-2 (LV circuit breakers), ANSI/IEEE C37.13 (US)
Control circuit wiring size (typical)2.5 mm² (minimum) copper, rated for control voltage
Main terminal torque (indicative — verify to manufacturer)20–80 Nm depending on conductor size and terminal design

Safety warnings

Tools needed

Common mistakes

Troubleshooting

ACB trips on closing without apparent overload
Cause: Instantaneous trip setting is too low, there is a fault on the downstream circuit, or the motor operator is not allowing the contacts to close fully before the ETU measures an inrush. Fix: Check downstream circuit for fault conditions. Review ETU instantaneous pickup setting against the expected inrush currents of connected loads. If the setting is correct, perform a secondary injection test to confirm the ETU is calibrated.
ACB does not trip during a secondary injection test at the expected current
Cause: ETU settings are incorrect, the test set connections are wrong, or the current transformers are faulty. Fix: Verify the ETU settings match the coordination study values. Confirm the test set is injecting into the correct phase CT terminals. Check CT continuity and ratio. If the ETU fails to trip at a confirmed overcurrent, it requires factory calibration or replacement.
Shunt trip does not operate
Cause: Shunt trip coil supply is absent, coil has open-circuited, or the coil voltage rating does not match the supply. Fix: Measure voltage at the shunt trip coil terminals during a trip signal. If voltage is absent, trace the control circuit back to the control supply and relay. If voltage is correct but the breaker does not trip, measure coil resistance — an open-circuit coil requires replacement.
Main contacts overheat in service
Cause: Under-torqued main circuit terminals creating contact resistance, or main contacts are worn or burnt and not making full surface contact. Fix: Isolate and check terminal torque with a calibrated torque wrench. Inspect main contact surfaces for pitting or burning — replace contacts if worn beyond the manufacturer's wear limit. Re-torque all connections.

Frequently asked questions

What is the difference between an ACB and an MCCB?

An ACB uses open-air arc quenching and is typically rated from 800 A to over 6 000 A, designed for main incomer and bus protection. An MCCB (moulded-case circuit breaker) is a smaller, self-contained unit rated from around 16 A to 1 600 A, used for feeder and branch circuit protection. ACBs have adjustable electronic trip units and full withdrawable designs; MCCBs are usually fixed-trip.

What does a shunt trip coil do in an ACB?

A shunt trip coil allows the ACB to be tripped remotely by applying a voltage pulse (typically 24 V DC, 110 V AC, or 230 V AC depending on the coil specification) from an external signal — fire alarm, emergency stop button, generator interlock, or building management system. The shunt trip is momentarily energised; the breaker trips and its internal latch holds it open.

What is the function of the undervoltage release (UVR)?

The UVR continuously monitors the supply voltage across one or two phases. If voltage falls below a set threshold (typically 35–70% of rated voltage), the UVR trips the breaker. It is used to prevent re-energising a circuit on voltage restoration after a supply interruption — the breaker must be manually reset. It also protects motors from running on reduced voltage.

How is an ACB 'withdrawn' and what does this mean?

A withdrawable ACB mounts in a cradle that allows the breaker to be racked from the connected (service) position through an isolated (test) position to a fully withdrawn position where the main contacts are disconnected from the busbars but the control wiring remains connected. This allows safe maintenance and testing without de-energising the switchboard.

What routine maintenance does an ACB require?

ACBs require periodic maintenance including: cleaning of arc chutes and contact surfaces, inspection of main and arcing contact wear, lubrication of the operating mechanism per manufacturer's schedule, testing of the electronic trip unit with a secondary injection test set, and exercising the breaker through several open/close operations. Intervals depend on fault duty experienced and manufacturer recommendations.

Related diagrams

Free electrical calculators

Edit this diagram free in the online editor