Current Transformer (CT) Wiring: Connection Methods, Safety Rules, and Metering Circuits

Ct Wiring Diagram — circuit diagram showing component connectionsMainOutlet 1Outlet 2SwitchLight230V AC UtilityBasic Wiring Diagram
Current Transformer (CT) Wiring: Connection Methods, Safety Rules, and Metering Circuits — interactive diagram. Open it in the editor to customise components and wiring.

This is a free printable ct wiring diagram: download the diagram as SVG or open it and print to paper or PDF.

Understand how to wire a current transformer correctly, why the secondary must never be open-circuited, and how to connect a CT to energy meters, protection relays, and analysers.

A current transformer (CT) is an instrument transformer designed to produce a scaled-down alternating current in its secondary winding that is proportional to the primary current flowing through or around it. CTs allow the measurement and protection of high-current power circuits using low-range metering equipment and provide galvanic isolation between the primary (high-voltage, high-current) circuit and the instrumentation connected to the secondary.

The primary winding of a measurement CT is typically a single conductor passing through the CT core window — often the existing bus bar or cable conductor — making CTs easy to retrofit onto live circuits without interrupting the primary circuit. The secondary winding produces a standardised output current of either 1 A or 5 A at full rated primary current, allowing interchangeability with standard metering and protection equipment.

The most critical safety rule in CT use — and the rule that has caused more instrument transformer failures and electrical injuries than any other — is: never open-circuit the secondary of a CT while current is flowing in the primary. When the secondary is open-circuited, the core saturates because the primary magnetomotive force is no longer opposed by secondary current. This creates an extremely high voltage across the secondary terminals — potentially thousands of volts — sufficient to destroy insulation, damage connected equipment, and deliver a lethal electric shock to anyone contacting the open secondary terminals. Before disconnecting any secondary device, always short-circuit the CT secondary terminals first using the shorting links provided on the terminal block.

CT secondary wiring uses screened twisted-pair cable to maintain accuracy. The P1/P2 terminals denote the primary polarity markings (where applicable), and the S1/S2 terminals (or K/L in some standards) denote the secondary output. Polarity is critical for protection relay applications and energy metering: reversed S1/S2 polarity produces current flow in the wrong direction and will cause a protection relay to respond to the wrong power flow direction, or cause an energy meter to read backwards.

For three-phase metering, three single-phase CTs are typically used, one per phase. The secondary currents are wired to a standard terminal block arrangement with shorting links, from which the metering or protection equipment connects.

Current transformer (CT) wiring diagrams cover a wide range of applications from energy metering to protection relay circuits, but the term 'CT wiring diagram' also appears frequently in searches for the Bajaj CT 100 motorcycle — a popular commuter bike in South Asia. Whether you are documenting a measurement CT secondary circuit or the electrical system of a small motorcycle, a clear schematic reduces installation errors. The free Circuit Diagram Maker lets you build and share either type of diagram entirely in your browser.

How to wire ct wiring diagram

  1. Determine CT ratio, accuracy class, and burden requirement Before selecting a CT, confirm: (1) the maximum primary current to be measured, (2) whether the application is metering (accuracy class 0.2, 0.5, 1) or protection (class 5P, 10P with accuracy limit factor), (3) the connected burden in VA at the secondary current (1 A or 5 A), including cable resistance calculated from run length and conductor cross-section.
  2. Install the CT on the primary conductor For a window-type CT, pass the primary conductor through the CT core window. For a split-core CT, open the core, position around the conductor, and close and secure the core according to the manufacturer's instructions. Ensure the primary conductor is centred within the window. Verify that the P1 polarity marking on the CT core is oriented toward the supply source (for correct polarity in metering and protection applications).
  3. Connect secondary wiring with shorting links in place Before connecting any CT secondary wiring, confirm that the shorting links on the secondary terminal block are closed (shorting the S1 and S2 terminals). With shorting links in place, the CT secondary is safe to work on. Run screened twisted-pair cable from the CT secondary terminals (S1 and S2) to the secondary terminal block in the metering panel.
  4. Wire the secondary terminal block Connect S1 to the corresponding polarity terminal on the terminal block and S2 to the return terminal. Maintain polarity consistency — S1 is the polarity terminal. For three-phase circuits, use separate CT secondary circuits for each phase, each with its own shorting link facility. Wire secondary screens to the panel earth bar at the panel end only.
  5. Connect metering or protection equipment Wire the secondary terminal block to the energy meter, protection relay, or current analyser secondary current inputs. Verify polarity and phase connection order. Calculate total secondary burden (meter input impedance + cable resistance) and confirm it is within the CT's rated VA burden.
  6. Open shorting links to commission the CT With the metering equipment connected and verified, open (remove) the shorting links to allow secondary current to flow through the metering devices. Warning: shorting links must only be opened after all secondary connections are complete. Record that the shorting links have been removed in the commissioning record.
  7. Verify CT operation with primary current injection or load current Apply primary current (either by energising the load circuit or by primary current injection test set). Verify secondary current at the metering equipment input matches the expected value based on the CT ratio. Check polarity at the energy meter or protection relay by confirming correct power flow direction indication. Record measurements for commissioning records.

Specifications

Standard secondary rated currents1 A or 5 A (IEC 61869-2)
Metering accuracy classes (IEC 61869-2)0.1, 0.2, 0.2S, 0.5, 0.5S, 1 — higher number = lower accuracy
Protection accuracy classes (IEC 61869-2)5P, 10P — with accuracy limit factor (ALF), e.g. 5P20 = 5% error at 20× rated current
Secondary terminal markingsS1/S2 (IEC standard) or K/L (alternative IEC marking) — P1/P2 for primary polarity
Minimum secondary conductor cross-section2.5 mm² for 5 A secondary circuits (verify for run length and burden)
Applicable standardIEC 61869-1 (general), IEC 61869-2 (current transformers)
Maximum open-circuit secondary voltage warningCan reach hundreds to thousands of volts — open circuit is prohibited during primary energisation

Safety warnings

Tools needed

Common mistakes

Troubleshooting

Energy meter shows zero current or significantly low reading
Cause: Shorting links left closed (shorting secondary before meter), open circuit in secondary wiring, or CT ratio mismatch in meter configuration. Fix: Verify all shorting links are open. Check secondary wiring continuity from CT to meter. Verify the CT ratio programmed in the energy meter matches the physical CT ratio label.
Energy meter reads negative current or power
Cause: S1 and S2 terminals reversed (polarity inversion) at either the CT secondary terminals or the meter input terminals. Fix: With shorting links in place, reverse the S1 and S2 connections at the terminal block. Re-commission and verify positive power flow indication under normal load conditions.
Protection relay trips spuriously or fails to trip during testing
Cause: CT polarity error (spurious trips), CT accuracy class insufficient for protection application (failure to trip), or CT secondary burden exceeding rated VA causing saturation. Fix: Verify polarity by primary injection. Verify CT accuracy class and rated accuracy limit factor meets protection relay requirements. Calculate total secondary burden and compare with CT rated VA.

Frequently asked questions

What happens if you open-circuit a CT secondary?

An open-circuited CT secondary while primary current is flowing causes the transformer core to saturate and generates a dangerously high voltage across the open secondary terminals — potentially thousands of volts. This can destroy insulation, damage connected equipment, and deliver a lethal shock. Always short-circuit the secondary before disconnecting any secondary device. This is the single most important CT safety rule.

What does CT ratio mean?

CT ratio is the ratio of the rated primary current to the rated secondary current. A 200/5 A CT means 200 A flowing in the primary produces 5 A in the secondary. A 1000/1 A CT means 1000 A primary produces 1 A secondary. The ratio determines the scaling factor applied to secondary meter readings to obtain the primary current value. Always verify the CT ratio matches the metering equipment input range.

What is the difference between a metering CT and a protection CT?

Metering CTs are designed for high accuracy at normal load currents and saturate at relatively low multiples of rated current to protect connected instruments. Protection CTs must maintain accuracy at large fault current multiples (typically up to 20× or more rated current) so protection relays operate correctly during faults. Using a metering CT for protection applications can result in failure to trip during faults. The CT's rated accuracy class (e.g. 0.5 for metering, 5P20 for protection) defines this characteristic.

What is CT burden and why does it matter?

Burden is the impedance of the connected secondary circuit — the total impedance of the wiring, metering devices, and any other loads on the secondary. A CT is designed to operate within a specified VA burden at rated secondary current. Exceeding the rated burden degrades measurement accuracy, and in extreme cases can cause core saturation and excessive secondary voltage. Always calculate the total secondary burden (including cable impedance) and verify it is within the CT's rated VA.

Why must CT secondary cables be screened?

CT secondary cables carry small analogue currents (typically 1 A or 5 A) that can be corrupted by electromagnetic interference from the primary conductors or nearby power equipment. Screened (shielded) cable prevents induced noise from distorting the secondary current waveform. The screen should be earthed at one end only (typically at the metering panel) to prevent circulating earth currents.

Where can I find the wiring diagram for a Bajaj CT 100?

The Bajaj CT 100 is a 100 cc single-cylinder motorcycle whose wiring diagram shows the battery, CDI unit, magneto stator, ignition coil, kill switch, horn, indicator relay, headlight, and tail/brake light circuits. Original diagrams are included in the factory service manual available from Bajaj authorised dealers. Third-party copies are widely shared in enthusiast forums. You can recreate or annotate the diagram using a free online schematic editor for reference or modification purposes.

Related diagrams

Free electrical calculators

Edit this diagram free in the online editor