Light Circuit Diagram

Light circuit diagram — circuit diagram showing component connectionsBreakerSwitchLight230V AC UtilityLight Switch Wiring
Light Circuit Diagram — interactive diagram. Open it in the editor to customise components and wiring.

This is a free printable light circuit diagram: download the diagram as SVG or open it and print to paper or PDF.

A light circuit diagram shows how switches, luminaires, and supply cables connect in single-way, two-way, and intermediate switching arrangements for domestic and commercial lighting.

A lighting circuit diagram defines the wiring arrangement connecting the mains supply to one or more luminaires (light fittings) via switches, providing control over when and how the lights operate. Understanding the circuit topology is essential for safe installation, fault diagnosis, and compliant wiring that meets the applicable national standard.

The simplest arrangement is the single-pole single-way switch controlling one luminaire. The live (line) conductor passes through the switch — interrupting the supply to the luminaire when open and completing the circuit when closed. The neutral conductor connects directly from the supply to the luminaire without interruption. The protective earth connects to the luminaire body and any metallic enclosure.

The loop-in method, which is standard in the UK and many countries following BS 7671, runs the supply into the ceiling rose or luminaire first, then loops out to the next rose, and runs a switch drop to the wall switch. The switch drop carries the line conductor down to the switch and returns the switched live back up to the luminaire. The advantage of loop-in wiring is that all connections are made at accessible points (ceiling roses) without junction boxes, simplifying inspection and maintenance.

The two-way switching arrangement allows a luminaire to be controlled from two separate switch positions — for example, at the top and bottom of a staircase. Two single-pole two-way switches are connected with two interlinks (the straps) between their common terminals and the two strappers. Switching either switch changes the state of the circuit and toggles the light. The live feeds the common of the first switch; the switched live returns from the common of the second switch to the luminaire.

Intermediate switching adds one or more intermediate switches between two two-way switches, allowing control from three or more positions. Each intermediate switch crosses the two strap connections and provides an additional toggle point.

Modern dimmer switches and electronic occupancy sensors replace the simple switch mechanism but connect at the same points in the circuit. Not all dimmer types are compatible with all lamp types — LED dimmers must be specified for LED loads; conventional TRIAC leading-edge dimmers are incompatible with most LED drivers.

All lighting circuit installation must comply with IEC 60364, BS 7671, NEC/NFPA 70, or AS/NZS 3000 and be performed by a qualified electrician.

How to wire light circuit diagram

  1. Determine the switching arrangement required Before designing or wiring a lighting circuit, establish: how many luminaires will be on the circuit; from how many switch positions each luminaire must be controlled (one position = single-way; two positions = two-way; three or more = intermediate switching). The switching arrangement determines which switch type and how many interlink conductors are needed.
  2. Plan the cable routes and calculate the circuit load Calculate the total wattage of all luminaires on the circuit. For LED lighting, the wattage is low — typically 5–20 W per fitting — so a standard 6 A or 10 A lighting circuit can supply many luminaires. Verify the total load does not exceed 80% of the circuit breaker rating for continuous loads. Plan cable routes that avoid damage-prone locations, crossing live circuits where possible, and that maintain minimum bending radii.
  3. Install the switch back box and run the switch drop cable Install the wall switch back box at the specified height (typically 1 200–1 400 mm from finished floor in residential, or as specified by the project). Run the switch drop cable from the ceiling rose position to the switch box. This cable carries the live conductor down and the switched live back up — in many wiring conventions, the returning switched live is re-identified with red or brown tape at the switch end where it appears as a neutral-coloured wire.
  4. Make connections at the ceiling rose or luminaire At the ceiling rose or luminaire, connect the incoming supply live to the switch live terminal block (looping it forward to the next rose if using loop-in method). Connect the returned switched live from the switch to the lamp terminal. Connect the neutral directly to the lamp neutral terminal. Connect the supply neutral to the loop-out neutral if applicable. Connect the protective earth to the luminaire earth terminal and loop it to the next rose.
  5. Connect the switch At the wall switch, identify the incoming live conductor and the returning switched live. On a single-way switch, connect the live to one terminal and the switched live to the other. On a two-way switch, connect the live to the COM terminal of the first switch and the switched live from the COM terminal of the second switch back to the luminaire. Connect the two strap conductors between the L1 and L2 terminals of both switches.
  6. Test before covering or plastering Before closing back boxes or completing any surface finish, test each circuit with a multimeter: verify supply voltage is present at the luminaire when switched on; verify no voltage is present at the luminaire (or only at the line-side of the switch) when switched off. On new installations, an insulation resistance test (500 V DC, ≥ 1 MΩ) between conductors and earth is required by IEC 60364, BS 7671, and AS/NZS 3000 before energising.

Specifications

Switch type for single-position controlSingle-pole single-way (SPST)
Switch type for two-position controlSingle-pole two-way (SPDT) — two required
Switch type for three or more positionsIntermediate switch (DPDT cross-wired) — one per additional position
Standard residential lighting circuit rating (UK/international)6 A MCB (approximately 1 380 W at 230 V)
Cable cross-section (typical lighting circuit)1.0 mm² or 1.5 mm² (verify per standard and derating)
Switch interruptsLine (live) conductor only — neutral never switched
Insulation resistance test voltage500 V DC (IEC 60364, BS 7671); minimum 1 MΩ
Applicable standardsIEC 60364, BS 7671, NEC/NFPA 70, AS/NZS 3000

Safety warnings

Tools needed

Common mistakes

Troubleshooting

Luminaire does not illuminate when switch is closed
Cause: Open circuit in supply, blown lamp, tripped circuit breaker, open switch contact, or broken cable conductor Fix: Check the circuit breaker is not tripped. Measure voltage at the luminaire terminals with switch closed — if zero, trace supply back through the switch and supply cable. Measure voltage at the switch output (switched live) terminal — if zero with switch closed, the switch or its connection is faulty. If voltage is present at the luminaire but it does not light, the lamp or driver has failed.
Two-way switching does not work correctly — light stays on or off regardless of switch position
Cause: Strapper wires (interlinks) crossed or incorrectly connected; both two-way switches connected in single-way mode; wiring error at the ceiling rose returning to incorrect terminal Fix: With the circuit de-energised, trace the three-core strapper cable between the two switches. Verify L1 of switch 1 connects only to L1 of switch 2, and L2 of switch 1 connects only to L2 of switch 2 (or the reverse — both consistent). Verify the live connects to the COM of switch 1 only, and the switched live returns from the COM of switch 2 only. Re-draw the connections if the circuit is not clear.
LED luminaire flickers or dims incompletely on a dimmer circuit
Cause: Dimmer is incompatible with the LED driver type in the luminaire; minimum load requirement of the dimmer is not met by the low-wattage LED load; LED driver is not dimmable Fix: Confirm the luminaire's LED driver is rated as dimmable — non-dimmable drivers do not respond to dimmer control and may flicker or fail. Verify the dimmer is rated for LED loads (trailing-edge or universal type). Check the dimmer's minimum load rating — some dimmers require a minimum load (e.g., 25 W) which modern low-wattage LEDs may not reach, causing instability. Use an LED-compatible dimmer matched to the specific LED lamp type.

Frequently asked questions

Why does a switch interrupt the live wire and not the neutral?

Interrupting the live conductor ensures that when the switch is open, the luminaire is de-energised — no live voltage is present at the lamp holder or fitting. If the neutral were switched instead, the luminaire would remain at line voltage on the live conductor even when switched off, creating a shock hazard during lamp replacement. National wiring standards (BS 7671, IEC 60364, NEC) require that single-pole switches interrupt the line (live) conductor.

What is a two-way switch and when is it used?

A two-way switch has three terminals: a common (COM) and two strap terminals (L1 and L2). It connects the common to either L1 or L2 depending on its position — it never disconnects both simultaneously. Two-way switches are used in pairs to control a luminaire from two locations (top and bottom of a staircase, both ends of a hallway). Changing either switch toggles the circuit state between on and off, regardless of the other switch position.

What is the loop-in wiring method?

The loop-in method connects the supply live and neutral into the ceiling rose or luminaire and loops the same supply conductors on to the next luminaire in the circuit. A switch drop takes the live from the rose down to the wall switch, and the switched live returns to the rose to feed the lamp. All connections are made at the ceiling rose positions rather than in junction boxes, which simplifies circuit tracing and maintenance. This method is standard in UK domestic wiring under BS 7671.

Can I connect an LED downlight to a circuit that previously had a halogen fitting?

Generally yes, but verify the circuit wiring is adequate. If the circuit was wired for the higher current of halogen fittings, the wiring will comfortably handle the lower current of LEDs. However, if a dimmer switch is installed on the circuit, verify that the dimmer is rated for LED loads — most older TRIAC leading-edge dimmers are not compatible with LED drivers and cause flickering, buzzing, or incomplete dimming range. Replace with an LED-compatible dimmer if necessary.

Why does my light stay on when I switch it off?

A light that remains weakly illuminated after switching off is a symptom of induced or backfeed voltage in the switch wire — common with long cable runs, cables routed in parallel with other live circuits, or certain electronic switch designs (wireless switches that derive their supply through the lamp). The small induced current is enough to keep some LED drivers partially powered. Solutions include a Zener diode suppressor at the lamp, a bleed resistor, or a dimmer switch with an internal resistor matched to the specific LED lamp.

Full written guides

Related diagrams

Free electrical calculators

Edit this diagram free in the online editor