Panel Wiring Diagram

Panel Wiring Diagram — circuit diagram showing component connectionsMain MCB 63ABreaker 1 - 20ABreaker 2 - 15ABreaker 3 - 20AKitchen OutletsLightingGeneral OutletsEarth Bus230V AC UtilityDistribution Panel / DB BoardMain MCB feeds individual circuit breakers
Panel Wiring Diagram — interactive diagram. Open it in the editor to customise components and wiring.

This is a free printable panel wiring diagram: download the diagram as SVG or open it and print to paper or PDF.

A panel wiring diagram shows how the incoming mains supply is distributed through a consumer unit or distribution board — with circuit breakers, RCDs, and wiring colour coding — providing the essential reference for any electrical installation or fault diagnosis.

An electrical distribution panel (also called a consumer unit, fuseboard, breaker panel, or load centre depending on the country) is the central point where mains electricity is received, metered, and distributed to individual circuits throughout a building.

Main components: - Main switch or main circuit breaker: disconnects all circuits simultaneously. In a single-phase domestic board, this is typically a double-pole switch rated 80–100 A. In a 3-phase board, a triple-pole (or four-pole with neutral) main switch is used. - Incoming supply terminals: the live (line), neutral, and earth conductors from the utility meter or upstream protection. These are live whenever the utility supply is connected — they are NOT isolated by the main switch in most designs. - Busbars: the copper bars that distribute incoming line and neutral to individual circuit breakers and RCDs. - RCD (Residual Current Device) / RCCB: detects earth leakage current (typically tripping at 30 mA) and disconnects the circuit. Mandatory for socket outlets, bathroom circuits, and outdoor wiring in most codes. - RCBO (Residual Current Circuit Breaker with Overcurrent): combines overcurrent protection and RCD in one device per circuit — preferable over whole-board RCDs because a fault on one circuit does not trip unrelated circuits. - MCBs (Miniature Circuit Breakers): provide overcurrent (overload and short-circuit) protection for individual circuits. Rated in amperes (6 A, 10 A, 16 A, 20 A, 32 A, etc.) and trip characteristics (B, C, D type).

Wiring colour standards vary by country: - IEC/EU/UK (post-2004): Line = Brown, Neutral = Blue, Earth = Green/Yellow - North America (NEC): Hot = Black (or Red for second hot), Neutral = White, Ground = Green or bare - Australia/NZ (AS/NZS 3000): Active = Brown (or Red in older work), Neutral = Blue (or Black), Earth = Green/Yellow

Panel sizing: The number and rating of circuits, total connected load, and diversity factor determine the main switch rating and incoming cable size. Distribution panels must be installed by a licensed electrician in almost all jurisdictions.

How to wire panel wiring diagram

  1. Isolate the supply before any panel work Contact the utility company to arrange isolation of the supply at the meter if you need to work on incoming terminals. For work on load-side circuits only, switch off and lock the main switch, and verify dead at every circuit breaker output before touching any wiring.
  2. Draw the panel layout before starting installation Plan which circuits occupy which breaker positions, the grouping of circuits under each RCD (if using split-board design), and where incoming supply and earth connections will be made. Label every circuit on the panel schedule inside the cover.
  3. Install and earth the panel enclosure Mount the panel at the correct height and location per local regulations. Bond the panel enclosure to the protective earth system. In TN-S or TN-C-S systems, the main earthing terminal connects here.
  4. Install the main switch and RCDs/RCBOs Clip circuit protective devices into the DIN rail. Ensure the main switch is at the top. Group circuits logically — lighting on one RCD, power on another, or use individual RCBOs for complete independence. Note that some RCDs require correct installation orientation.
  5. Connect incoming supply to the main switch Only after utility isolation: connect the incoming Line to the top of the main switch, Neutral to the neutral bar, and Earth to the main earth terminal. Use the correct conductor cross-section and terminal torque per the panel and cable specifications.
  6. Wire individual circuits to their breakers Terminate each circuit's line conductor (brown/black/red depending on region standard) to its MCB or RCBO, neutral to the neutral bar, and CPC (earth) to the earth bar. Observe the panel's wiring regulations for conductor cross-sections and insulation temperature ratings.
  7. Test each circuit before energising under load Perform insulation resistance and continuity tests on each circuit before restoring supply. Test RCD trip times with a calibrated RCD tester. Verify all breakers are correctly labelled on the schedule. Restore supply and check each circuit at normal load.

Specifications

Standard (UK)BS 7671:2018+A2:2022 (IET Wiring Regulations 18th Edition)
Standard (US)NEC / NFPA 70 (current edition)
Standard (international)IEC 60364 series
RCD trip current (standard)30 mA (general; 100 mA for time-delayed, 10 mA for medical)
Line conductor colour (IEC/UK)Brown (single-phase); Brown/Black/Grey (3-phase)
Neutral conductor colour (IEC/UK)Blue
Earth conductor colourGreen/Yellow striped
MCB typesType B: 3–5× In; Type C: 5–10× In; Type D: 10–20× In

Safety warnings

Tools needed

Common mistakes

Troubleshooting

RCD trips immediately when restored
Cause: A circuit connected to the RCD has an earth leakage fault — damaged cable insulation, moisture in an accessory, or a faulty appliance. Fix: Switch off all MCBs under the RCD. Reset the RCD. Turn on each MCB one at a time — the RCD will trip when the faulty circuit is energised. Identify and repair the fault on that circuit (insulation resistance test, appliance disconnect, cable inspection).
MCB trips repeatedly on a specific circuit
Cause: The circuit is overloaded (too many loads), there is a short circuit in the wiring or an appliance, or the MCB is undersized for the load. Fix: Disconnect all loads. Reset the MCB — if it trips immediately, there is a wiring fault (short circuit). Reconnect loads one at a time. If it trips only under full load, calculate the total load and compare to the MCB rating.
Neutral bar overheating
Cause: Loose neutral connection causing high resistance and arcing, or multiple neutrals clamped in a single terminal. Fix: Isolate the supply immediately. Open the panel and inspect every neutral terminal for heat discolouration, burning, or loose conductors. Re-terminate with one conductor per terminal at the correct torque setting.

Frequently asked questions

What is the difference between an MCB and an RCBO?

An MCB (Miniature Circuit Breaker) provides overcurrent protection only — it trips on overload and short-circuit current, but will not disconnect a dangerous earth leakage fault. An RCBO combines an MCB and an RCD in a single device, providing both overcurrent and earth leakage protection for one circuit, so a fault on that circuit does not affect others sharing a common RCD.

What is a Type B, Type C, and Type D MCB, and which should I use?

The letter refers to the trip threshold for magnetic (instantaneous) operation: Type B trips at 3–5× rated current (for resistive loads — lighting, heating), Type C at 5–10× (for motor and transformer loads with moderate inrush), and Type D at 10–20× (for heavy motor loads and transformers with high inrush). Use Type B for most residential circuits and Type C for circuits feeding motors or electronic equipment.

Why should the incoming supply terminals never be touched, even with the main switch off?

The incoming supply terminals (on the utility side of the main switch) are connected directly to the electricity meter and remain live even when the main switch is open. Accessing these requires isolation by the utility company or an approved meter operator. They are a lethal electrocution risk at all times.

Why does one tripped MCB take out multiple circuits in some panels?

If multiple circuits share a single upstream RCD and the tripped device is the RCD (not the MCB), all circuits on that RCD will de-energise. In boards using split-load RCDs (where half the circuits are on each RCD), a fault on one circuit takes out all circuits on that RCD. Fitting RCBOs to each circuit individually eliminates this problem.

Do I need an RCD on every circuit in a residential distribution panel?

Requirements vary by country. Under BS 7671 (UK), RCD protection is required for all socket circuits, all circuits in zones 0–2 of bathrooms, and any circuits in external locations or embedded in walls at less than 50 mm depth without metallic covering. Under NEC (US), GFCI protection is required for specific locations (bathrooms, kitchens, outdoors, garages). Always check the applicable edition of your local code.

Related diagrams

Free electrical calculators

Edit this diagram free in the online editor