Star-Delta Circuit Diagram — Three-Phase Motor Starter

Star Delta Circuit Diagram — circuit diagram showing component connections3-Phase SupplyFuse 63AKMain Contactor KM1KStar Contactor KM2KDelta Contactor KM3Overload RelayM3~Motor M1230V AC UtilityStar-Delta Motor StarterStar for start, delta for runOL relay protects motor
Star-Delta Circuit Diagram — Three-Phase Motor Starter — interactive diagram. Open it in the editor to customise components and wiring.

This is a free printable star delta circuit diagram: download the diagram as SVG or open it and print to paper or PDF.

The star-delta circuit diagram shows how three contactors and a timer relay reduce inrush current when starting a large three-phase induction motor. By connecting motor windings in star (Y) first and switching to delta (Δ) after acceleration, starting current is limited to one-third of the direct-on-line value — protecting the supply, the motor, and driven machinery from damaging current spikes.

A star-delta starter uses three contactors (main, star, and delta) and a time-delay relay to implement a two-stage starting sequence for three-phase squirrel-cage induction motors. In the first stage, the main contactor and star contactor close simultaneously, connecting the motor windings in a star configuration. In star connection, each winding sees only the line voltage divided by √3 (approximately 58% of full voltage). This reduces starting current to one-third of direct-on-line value and starting torque to one-third of full-voltage torque. After a preset time (typically 5–15 seconds), the star contactor opens and the delta contactor closes, reconnecting the motor windings in delta. In delta connection, each winding sees the full line voltage, and the motor develops full rated torque. The changeover sequence must be: star opens first, a brief pause (50–100ms) to allow residual flux to decay, then delta closes. Opening star before closing delta is critical — simultaneous operation would momentarily short-circuit two winding phases through overlapping contactor contacts, producing a current spike larger than direct-on-line. The time-delay relay controls this sequence automatically. For the star-delta connection to function, the motor must have all six winding terminals accessible (labeled U1, V1, W1 on one end and U2, V2, W2 on the other). Single-star-only motors with only three accessible terminals cannot be star-delta started. In the star connection, U2, V2, W2 are shorted together through the star contactor. In the delta connection, U1 connects to W2, V1 to U2, and W1 to V2 through the delta contactor — forming the closed triangle. The main contactor carries full load current in both stages and must be rated accordingly. The star contactor carries reduced current (1/√3 of main current) and can be one frame size smaller. The delta contactor carries winding current which is 1/√3 of line current in delta operation — also potentially a smaller rating than the main. A thermal overload relay on the main contactor protects against sustained overcurrent in both starting stages. Modern soft starters and variable frequency drives have largely replaced star-delta starters in new installations, but star-delta remains common in existing industrial plants and in cost-sensitive applications up to 200kW.

How to wire star delta circuit diagram

  1. Select and size the three contactors Size the main contactor for full-load current (FLC) of the motor. The star contactor carries FLC/√3 — may be one frame smaller. The delta contactor also carries FLC/√3 (winding current in delta). Include a thermal overload relay in the main contactor circuit rated for the motor FLC. Ensure each contactor has both mechanical and electrical interlock capability.
  2. Wire the power circuit Connect three-phase supply L1-L2-L3 to the main contactor (KM) input terminals. Connect KM output to motor terminals U1, V1, W1. Connect the delta contactor (KD) between U1-W2, V1-U2, W1-V2 (cross-connection for delta). Connect the star contactor (KY) to short U2, V2, W2 together. The star point formed by KY is the temporary neutral during star starting.
  3. Wire the control circuit Wire the control circuit (typically 24V DC or 110V AC from a control transformer). The START button energizes the main contactor KM and the star contactor KY simultaneously, and starts the timer relay KT. The timer output (normally open, timed-close) energizes the delta contactor KD after the preset time. Simultaneously, KD's normally closed auxiliary contact de-energizes the star contactor KY — completing the changeover.
  4. Install interlocks between star and delta contactors Wire a normally closed (NC) auxiliary contact of the delta contactor KD in series with the star contactor KY coil circuit — if KD is energized, KY cannot energize. Wire a NC auxiliary contact of KY in series with KD coil — if KY is energized, KD cannot energize. This electrical interlock prevents simultaneous closure even if the timer malfunctions. Also install mechanical interlocks if contactors are adjacent.
  5. Test the sequence with a clamp meter Apply power and press START. Verify with a clamp meter that line current rises to approximately 2–3 times FLC (star starting current) and begins decreasing as the motor accelerates. At timer expiry, observe the current briefly spike (transition) and settle to the delta running current (FLC or less at partial load). Adjust the timer if the transition current exceeds 6× FLC, indicating transition occurring before the motor reached sufficient speed.

Specifications

Starting Current≈2×FLC in star (vs 6×FLC direct-on-line)
Starting Torque1/3 of full-voltage torque
Changeover Timer5–15 seconds (adjustable)
Motor RequirementSix accessible terminals (U1,V1,W1,U2,V2,W2)

Safety warnings

Tools needed

Common mistakes

Troubleshooting

Motor starts but does not accelerate to full speed after transition
Cause: Motor delta wiring is incorrect — terminals connected U1-U2, V1-V2, W1-W2 (direct short across windings) instead of the cross-connection needed for delta Fix: Isolate power. Verify delta contactor wiring connects U1 to W2, V1 to U2, and W1 to V2. The cross-connection is essential — direct connection between same terminal pairs shorts each winding rather than forming a triangle.
Main breaker trips at the moment of star-to-delta transition
Cause: Star-to-delta changeover time is too short, or dead time between star opening and delta closing is absent, causing a transition current spike exceeding breaker trip threshold Fix: Increase the timer set point by 3–5 seconds to allow more motor acceleration before transition. Verify there is a 50–100ms dead time between star contactor opening and delta contactor closing — some timers include a built-in transition delay, others require an additional timing relay.
Star contactor welds (fuses closed) after repeated starts
Cause: Contactor undersized — the star contactor was selected for running current only, not the higher starting current it must interrupt during the star-to-delta transition Fix: Replace star contactor with one rated for the full starting current (same frame as main contactor). The star contactor interrupts current equal to starting current at the moment of transition — it must be rated for this duty, not just the reduced star running current.

Frequently asked questions

Why does star-delta reduce starting current to one-third?

In star connection, each motor winding sees the line voltage divided by √3 (approximately 58%). Current is proportional to voltage, so winding current drops to 1/√3 of the direct-on-line value. Line current equals winding current in star, so line current is also 1/√3 of DOL. Since power is proportional to current squared times resistance, torque also drops to (1/√3)² = 1/3 of full-voltage torque.

How long should the star timer be set to?

Typical settings are 5–15 seconds, depending on motor size and load inertia. Set the timer so the motor reaches at least 75–80% of its rated speed before transition. Too short a time causes a large transition current spike; too long keeps the motor in inefficient star configuration. Use a clamp meter to watch the starting current — the timer should switch when current has dropped close to full-load current.

Can star-delta starting be used with all three-phase motors?

No — only motors with all six winding terminals accessible (dual-voltage or star-delta-capable motors). Single-voltage motors wound internally in star have only three accessible terminals and cannot be externally reconnected. Check the motor nameplate for terminal designations: six terminals (U1, V1, W1, U2, V2, W2) confirms star-delta compatibility. Also, the motor must be rated for delta (lower) voltage at its nameplate voltage — a 415V star motor cannot be delta-started on a 415V supply.

What causes a large current spike during star-delta transition?

Current spikes during transition have two causes: (1) the motor still has residual flux when delta closes, creating a flux difference between the field and the supply that drives a large transient current; (2) if star and delta overlap (close-before-open transition), the overlap shorts winding phases. Both are mitigated by using an open-transition changeover with a 50–100ms dead time between star opening and delta closing.

What is the difference between a star-delta starter and a soft starter?

A star-delta starter uses three contactors to step-change voltage in two stages, producing two discrete current levels and a transition transient. A soft starter uses thyristors (SCRs) to continuously ramp supply voltage from zero to full, providing smooth current control throughout the entire acceleration ramp without any transient. Soft starters cost more but eliminate the transition spike, extend motor and mechanical life, and provide additional protection features (phase loss, motor temperature, current limit).

Related diagrams

Free electrical calculators

Edit this diagram free in the online editor