Breaker Diagram

Breaker Diagram — circuit diagram showing component connectionsMain MCB 63ABreaker 1 - 20ABreaker 2 - 15ABreaker 3 - 20AKitchen OutletsLightingGeneral OutletsEarth Bus230V AC UtilityDistribution Panel / DB BoardMain MCB feeds individual circuit breakers
Breaker Diagram — interactive diagram. Open it in the editor to customise components and wiring.

This is a free printable breaker diagram: download the diagram as SVG or open it and print to paper or PDF.

A technical reference for circuit breaker panel wiring diagrams, covering single-pole, double-pole, and GFCI/AFCI breakers in residential and light commercial distribution boards.

A circuit breaker diagram — sometimes called a panel diagram or load centre diagram — illustrates how individual circuit breakers connect the incoming electrical supply to branch circuits throughout a building. Understanding this diagram is fundamental to any electrical installation, fault diagnosis, or load balancing task.

In a residential main distribution board (MDB), the incoming supply from the utility passes through a main disconnect breaker (or main switch) before being distributed across two bus bars (in a 120/240V split-phase North American system) or a single live bar and neutral bar (in a single-phase 230V system). Branch circuit breakers clip to these bus bars, with their load terminals feeding individual circuits.

In a 120/240V split-phase system (standard in North America), single-pole breakers connect to one bus bar phase (120V to neutral), and double-pole breakers span both bus bars (240V for large appliances such as dryers, ranges, and HVAC units). The two bus bars are supplied by a centre-tapped distribution transformer, giving 120V from either bus to neutral and 240V across the two buses.

In a 230V single-phase system (standard in most of Europe, UK, Africa, Australia, and much of Asia), the panel has a single live supply, neutral, and earth. Single-pole breakers switch the live only.

In a three-phase 400V/415V distribution board, three bus bars are present. Single-pole breakers connect to one phase (230V to neutral), and three-pole breakers connect to all three phases (400V across phases) for three-phase equipment.

Modern panels increasingly require arc fault circuit interrupter (AFCI) breakers for bedroom and living area circuits and ground fault circuit interrupter (GFCI/RCD) breakers for wet area circuits — requirements specified in NEC 2023, BS 7671:2018, and equivalent national codes. GFCI/AFCI breakers replace standard breakers in the same slot but have additional pigtail neutral wires that must connect to the neutral bar.

How to wire breaker diagram

  1. Read and understand the panel diagram before working Locate the circuit directory on the inside of the panel door. Identify the main disconnect rating, each branch circuit breaker rating, and which load each serves. Note which breakers are single-pole, double-pole, GFCI, or AFCI types. Identify the neutral bar and earth bar (some panels have combined neutral/earth bars; others have separate ones).
  2. Isolate the panel safely To work on an individual branch circuit: switch the branch breaker to OFF and test the outlet or fixture with a non-contact tester to confirm dead. To work in the panel itself: switch the main disconnect to OFF. Note — even with the main disconnect OFF, the incoming service wires from the utility remain live. Do not touch these wires; they are energised at all times unless the utility disconnects service at the meter.
  3. Install a new branch circuit breaker Select a breaker of the correct brand and type for the panel (breakers are not universally interchangeable across brands — mixing brands is unsafe and prohibited by most codes). Align the breaker with the bus bar and press firmly until the clip snaps onto the bar. Connect the branch circuit live wire to the breaker load terminal. For GFCI/AFCI breakers, also connect the white pigtail from the breaker to the neutral bar.
  4. Connect the neutral and earth Connect the circuit neutral (white or blue) to the neutral bar using the provided torque terminal. Connect the circuit earth (green or bare copper) to the earth bar. In the main panel, neutral and earth bars are typically bonded together. In a sub-panel, they must be separate — the neutral is isolated, and only the earth bar bonds to the sub-panel chassis.
  5. Verify torque values and label the breaker Tighten all terminal connections to the manufacturer's specified torque — loose connections are the leading cause of panel overheating and fire. Use a calibrated torque screwdriver where required by code. Update the circuit directory label with the breaker number, rating, and the circuit it serves before closing the panel.

Specifications

Standard residential panel voltage (North America)120/240V AC single-phase split
Standard residential panel voltage (international)230V AC single-phase or 400V AC three-phase
Standard service entrance size (residential)100 A or 200 A
GFCI trip threshold5 mA ground fault current, trip time < 40 ms
AFCI requirement (NEC 2023)Required on all 15 A and 20 A 120V branch circuits in dwelling units
Terminal torque (typical breaker terminal)Approximately 2.25–3.4 N·m — verify from breaker manufacturer datasheet
Minimum wire size for 15 A circuit14 AWG copper (NEC) / 1.5 mm² (IEC)
Minimum wire size for 20 A circuit12 AWG copper (NEC) / 2.5 mm² (IEC)

Safety warnings

Tools needed

Common mistakes

Troubleshooting

Breaker trips immediately when reset
Cause: A short circuit or ground fault exists on the circuit — live conductor is in contact with neutral or earth Fix: Disconnect all loads and outlets on the circuit. Measure resistance between the live and neutral conductors and between live and earth with a multimeter. A near-zero reading confirms a short or fault. Trace the circuit to find the fault location before restoring the breaker.
GFCI breaker trips immediately and will not reset
Cause: Ground fault present on the circuit, or the GFCI pigtail neutral is not connected to the neutral bar Fix: Verify the white pigtail wire from the GFCI breaker is firmly landed on the neutral bar. With the circuit disconnected, test for ground faults on the circuit wiring and all connected outlets. A GFCI breaker tests its own circuitry on reset — a defective GFCI module will also refuse to reset.
Breaker feels warm or hot to touch
Cause: The breaker is consistently operating near its rated current limit, or the terminal connection is loose or corroded Fix: Measure current draw on the circuit with a clamp meter. If the load is within rating, de-energise and check the terminal connection — a loose terminal creates a resistive hot spot. Tighten to the specified torque. If the terminal is discoloured or damaged, replace the breaker.
Circuit works intermittently — breaker does not appear to trip
Cause: Loose connection at the breaker terminal or at a downstream junction, or a thermal breaker cycling on temperature Fix: Inspect all terminal connections on the breaker and downstream. Check that the breaker clip is fully seated on the bus bar. Verify current draw is within the breaker rating. Intermittent connection faults are dangerous — trace and repair before leaving the circuit in service.

Frequently asked questions

What is the difference between a single-pole and double-pole breaker?

A single-pole breaker switches one conductor (the live/hot) and is used for 120V circuits (North America) or 230V single-phase circuits (international). A double-pole breaker switches two conductors simultaneously and is used for 240V circuits (North America) or 415V single-phase circuits (international), and for circuits where both live and neutral must be switched for isolation.

What does GFCI (or RCD) protection on a breaker do?

A GFCI breaker (Ground Fault Circuit Interrupter, called RCD or RCCB in international standards) monitors the difference in current between the live and neutral conductors. If this imbalance exceeds approximately 5 mA — indicating current is leaking to earth, possibly through a person — it trips in under 40 ms. It is required in bathrooms, kitchens, outdoor circuits, and garages by most national electrical codes.

How do I identify which breaker serves which circuit?

Every panel should have a circuit directory label on the inside door identifying each breaker by number and its connected load. If the label is missing or inaccurate, use a non-contact voltage tester or a circuit tracer (tone generator and probe) to identify circuits without energising wires. Never guess — breakers frequently serve non-obvious or multi-room circuits.

What causes a circuit breaker to trip repeatedly?

Repeated tripping indicates the circuit is operating at or above its rated capacity (overload), or a fault exists. If the breaker trips immediately on reset, a short circuit or ground fault is present. If it trips after several minutes under load, the circuit is overloaded and the total connected load must be reduced or the circuit redesigned.

Can I replace a standard breaker with a higher-rated one to stop it tripping?

No. The circuit breaker rating must match the installed cable size — the breaker protects the wire, not the appliance. Fitting a higher-rated breaker on undersized cable removes that protection and creates a fire risk. If the circuit is genuinely too small for the load, the cable must be upgraded by a licensed electrician before a higher-rated breaker is installed.

Full written guides

Related diagrams

Free electrical calculators

Edit this diagram free in the online editor