Control Diagram of Star Delta Starter: Timer, Interlocking and Transition Logic

Control Diagram Of Star Delta Starter — circuit diagram showing component connections3-Phase SupplyFuse 63AKMain Contactor KM1KStar Contactor KM2KDelta Contactor KM3Overload RelayM3~Motor M1230V AC UtilityStar-Delta Motor StarterStar for start, delta for runOL relay protects motor
Control Diagram of Star Delta Starter: Timer, Interlocking and Transition Logic — interactive diagram. Open it in the editor to customise components and wiring.

This is a free printable control diagram of star delta starter: download the diagram as SVG or open it and print to paper or PDF.

The star-delta starter control diagram shows how a timer relay coordinates three contactors to first connect the motor in star configuration for reduced-voltage starting, then transition automatically to delta after the programmed acceleration time.

Star-delta starting reduces motor starting current to approximately one third of direct-on-line (DOL) starting current by initially connecting motor windings in star, which applies line-to-neutral voltage (231 V on a 400 V system) across each winding rather than the full line-to-line voltage. After the motor accelerates to approximately 70–80 percent of full speed in star, the control circuit transitions the winding configuration to delta, restoring full line-to-line voltage across each winding for full-torque operation. The power circuit requires three contactors: the main contactor KM1 connects L1, L2, L3 to motor terminals U1, V1, W1 and remains closed throughout operation. The star contactor KM3 links motor terminals U2, V2, W2 together at a neutral point during starting. The delta contactor KM2 connects U2 to V1, V2 to W1, and W2 to U1 during running, forming the delta winding configuration. The control circuit operates as follows: pressing start energises the main contactor coil KM1 and the star contactor coil KM3 simultaneously, placing the motor in star. The timer relay TDR (time delay relay) starts timing simultaneously. When the TDR times out after the programmed star duration (typically 5–15 seconds), its time-delayed contact opens the star contactor coil KM3 and closes the delta contactor coil KM2. Crucially, an interlocking arrangement ensures KM2 and KM3 can never energise simultaneously, because simultaneous energisation would short-circuit the motor windings. The interlock is achieved by wiring a normally-closed auxiliary contact of KM3 in series with the KM2 coil, and a normally-closed auxiliary contact of KM2 in series with the KM3 coil. A short transition break of approximately 30 ms between star opening and delta closing allows flux in the motor windings to decay before delta connection, reducing the transition current transient. Some modern electronic star-delta timers incorporate this break-before-make timing internally.

How to wire control diagram of star delta starter

  1. Wire main contactor KM1 Connect L1, L2, L3 to KM1 input terminals 1, 3, 5. Connect KM1 output terminals 2, 4, 6 to motor terminals U1, V1, W1 via the overload relay. KM1 remains closed throughout star and delta operation.
  2. Wire star contactor KM3 Connect motor terminals U2, V2, W2 to KM3 main contacts so that when KM3 closes, all three motor winding ends are shorted together forming the star neutral point. KM3 line side terminals connect to a common bus.
  3. Wire delta contactor KM2 Wire KM2 to connect U2 to the junction of W1 and KM1-output L3, V2 to U1 and L1 junction, W2 to V1 and L2 junction — forming the delta cross-connections between winding ends and starts of adjacent phases.
  4. Wire control circuit Connect start button to KM1 coil. KM1 NO auxiliary powers KM3 coil and starts TDR. TDR time-delayed NC contact de-energises KM3. TDR time-delayed NO contact energises KM2. Wire KM2 NC aux in series with KM3 coil and KM3 NC aux in series with KM2 coil for interlocking.
  5. Commission and verify timing Power up with no load connected to motor shaft. Observe current on all three phases with a clamp meter during start. Verify current drops at star transition and confirm delta current equals rated FLA. Adjust TDR if star current has not reduced before transition.

Specifications

Star starting voltage per windingVline ÷ √3 = 231 V (on 400 V supply)
Starting current (star)≈33% of DOL locked-rotor current
Star period (typical)5–15 seconds (load dependent)
Transition break-before-make30–100 ms (timer or electronic relay)

Safety warnings

Tools needed

Common mistakes

Troubleshooting

Motor starts but does not transition to delta
Cause: TDR timer not functioning or TDR time-delayed contact not wired correctly Fix: Measure voltage at TDR coil terminals during start to confirm it is energised. Time the transition with a stopwatch. If TDR contacts do not operate, replace timer relay. Verify wiring matches TDR terminal diagram.
Overload trips at delta transition
Cause: Motor not fully accelerated before transition, causing large current spike on delta connection Fix: Increase star acceleration timer by 3–5 seconds. Verify motor current decreases in star before transition time. Check that load does not require more torque than available in star during acceleration.
KM2 and KM3 both try to energise
Cause: Electrical interlock not wired or NC auxiliary contacts failed open Fix: Immediately cut power. Inspect interlock wiring — NC auxiliary of KM3 must be in series with KM2 coil and vice versa. Replace any failed auxiliary contact blocks before re-energising.

Frequently asked questions

Why does star-delta starting reduce starting current?

In star connection, each motor winding sees line-to-neutral voltage (Vline divided by root 3, approximately 231 V on a 400 V supply). Motor starting current is proportional to applied voltage squared, so the current at 231 V is one third of current at 400 V. The trade-off is that starting torque is also reduced to one third of DOL torque, making star-delta unsuitable for loads requiring high starting torque.

How long should the star acceleration period be?

The star period should be long enough for the motor to reach 70–80 percent of synchronous speed before transitioning to delta. For most standard induction motors with low-inertia loads (pumps, fans), 5–10 seconds is typical. For higher-inertia loads, increase to 10–15 seconds. Monitor current during starting with a clamp meter — when running current in star drops and stabilises, the motor has accelerated sufficiently for delta transition.

What happens if the motor is still in star when the load is applied?

In star configuration, the motor produces only one third of its rated torque. If full load is applied while still in star, the motor may stall — particularly for loads requiring high torque at speed such as conveyors or compressors. The overload relay would eventually trip if the motor stalls in star. Always ensure the star period is sufficient for the motor to reach speed with the actual load before transitioning.

Can star-delta starters be used with all motors?

Star-delta starters require a motor with all six winding terminals accessible (U1, V1, W1, U2, V2, W2). Some smaller motors have only three terminals with the star or delta connection made internally — these cannot be used with star-delta starters. The motor must be rated for the lower star voltage: a motor rated 400 V delta must be suitable for 231 V in star, which is standard for 400/690 V dual-voltage motors.

What is the transition current spike and can it be reduced?

When transitioning from star to delta, the motor has residual flux and residual voltage that may be out of phase with the supply voltage at the instant of delta connection. If the phase difference is significant, the delta closure drives a large circulating current — potentially exceeding DOL locked-rotor current briefly. Electronic soft-starters or VFDs eliminate this issue entirely. Within star-delta starters, extending the timer break-before-make interval to 50–100 ms allows residual flux to decay, reducing transition spike.

Related diagrams

Free electrical calculators

Edit this diagram free in the online editor