Star Delta Starter Control Diagram with Timer
This is a free printable star delta starter control diagram with timer: download the diagram as SVG or open it and print to paper or PDF.
Detailed control circuit reference for a star-delta motor starter with timer relay showing contactor sequencing, interlocking, and transition logic.
A star-delta (wye-delta) starter reduces the starting current of a 3-phase induction motor by initially connecting the motor windings in star (wye) configuration and then, after a timed delay, switching them to delta configuration for normal running.
In star connection, each motor winding receives approximately 58% (1/√3) of the line voltage, reducing starting current to approximately one-third of the direct-on-line (DOL) starting current. This also reduces starting torque to approximately one-third of DOL torque. Once the motor approaches running speed, the timer relay initiates the transition to delta connection, where each winding receives full line voltage.
The control circuit requires three contactors: the main contactor (KM1 or K-Main), the star contactor (KM3 or K-Star), and the delta contactor (KM2 or K-Delta). A timer relay (KT) controls the star-to-delta transition delay.
Sequence of operation: 1. Start push button is pressed. The main contactor (KM1) energises, connecting the motor to the supply. Simultaneously, the star contactor (KM3) energises, connecting the motor winding ends to form the star point. The motor starts in star configuration. The timer (KT) starts. 2. After the timer preset time elapses (typically 6–15 seconds, set per the motor characteristics), KT contacts operate: the star contactor (KM3) de-energises, and after a brief interlock delay to avoid a phase-to-phase short, the delta contactor (KM2) energises, reconnecting the windings in delta. 3. The motor runs in delta configuration under full voltage.
Critical interlock: The star (KM3) and delta (KM2) contactors must be electrically and mechanically interlocked to prevent both from closing simultaneously (which would cause a short circuit).
Overload relay (OLR) in the power circuit monitors motor current. The OLR contact in the control circuit trips the starter on overload.
All wiring must comply with IEC 60947, NEC/NFPA 70, BS 7671, or AS/NZS 3000. A licensed electrician must perform all installation.
How to wire star delta starter control diagram with timer
- Verify motor suitability for star-delta starting Confirm the motor has six accessible terminal leads (U1, V1, W1, U2, V2, W2) and is rated for delta operation at the supply voltage. Check the motor nameplate: if the voltage rating shows 400 V Δ / 690 V Y, it is suitable for star-delta on a 400 V supply.
- Wire the power circuit Supply (L1, L2, L3) connects to the main contactor (KM1) input terminals. KM1 output terminals connect to the motor's U1, V1, W1 terminals and also to the delta contactor (KM2) input. The star contactor (KM3) bridges U2, V2, W2 (winding ends) together to form the star point.
- Wire the control circuit supply Derive the control circuit supply from two phases (or a separate control transformer for 24 V AC/DC control circuits). Protect the control circuit with a miniature circuit breaker (MCB). Terminate the neutral or negative at a common rail.
- Wire the start and stop push buttons The STOP button (NC contact) wires in series with the START button (NO contact) and the coil circuit. The START button energises KM1 and KM3, and the timer (KT) simultaneously. A KM1 auxiliary contact seals in the START button (latch/hold function).
- Wire the timer and star/delta transition logic The timer relay (KT) coil is energised by the same circuit that energises KM1. The KT timed-out contact is wired to de-energise KM3 (star) and energise KM2 (delta). Verify the timer type: on-delay timers de-energise KM3 and energise KM2 after the preset delay from start.
- Wire the interlocks between star and delta contactors An NC auxiliary contact from KM3 is wired in series with the KM2 coil circuit. An NC auxiliary contact from KM2 is wired in series with the KM3 coil circuit. This electrical interlock prevents simultaneous energisation. Mechanically interlocked contactor pairs provide additional protection.
- Wire the overload relay and test The overload relay (OLR) NC contact is wired in series with the main control circuit, so an overload trips all contactors. Set the OLR to the motor's full-load current. Test the sequence by energising the control circuit and verifying star-then-delta transition at the correct timer interval.
Specifications
| Starting current reduction (vs DOL) | Approximately 1/3 of DOL starting current |
|---|---|
| Starting torque reduction (vs DOL) | Approximately 1/3 of DOL starting torque |
| Winding voltage in star phase | VLine / √3 ≈ 58% of line voltage |
| Winding voltage in delta phase | Full line voltage |
| Typical timer setting range | 6 – 15 seconds (set to motor acceleration characteristics) |
| Number of contactors required | 3 (main, star, delta) |
| Applicable contactor duty class | AC-3 (squirrel cage motor starting) |
Safety warnings
- Star and delta contactors must be both electrically and mechanically interlocked. Simultaneous closure causes a phase-to-phase short circuit with potentially catastrophic fault current and fire risk.
- The motor must have all six winding terminals accessible and must be rated for delta connection at the supply voltage. Never connect a motor rated only for star at the supply voltage in a star-delta starter.
- Always include a properly rated overload relay in the power circuit. Size it to the motor's full-load current (delta operation). Incorrect OLR setting leaves the motor unprotected.
- All installation must be performed by a licensed electrician complying with IEC 60947, NEC/NFPA 70, BS 7671, AS/NZS 3000, or applicable industrial electrical codes.
- Verify the circuit is completely de-energised and locked out before servicing any contactor, timer, or push button.
Tools needed
- Calibrated digital multimeter (CAT III 600 V minimum)
- Clamp meter (for motor current measurement during commissioning)
- Insulated screwdrivers and crimping tools
- Lockout/tagout kit
- Timer relay with adjustable delay and datasheet
- Continuity tester for interlock verification
Common mistakes
- Using only electrical interlocking without mechanical interlocking between star and delta contactors — mechanical interlock is essential as an additional safety layer.
- Setting the timer too short for the motor to reach near-running speed in star, causing excessive current transient on transition to delta.
- Sizing the overload relay to the star current rather than the full-load delta current, leaving the motor underprotected in running mode.
- Not connecting KM1 auxiliary contact as a seal-in (hold) contact across the start button, causing the starter to drop out when the start button is released.
- Wiring U2, V2, W2 motor terminal connections incorrectly to the star or delta contactors, resulting in the motor failing to start or running in the wrong direction.
Troubleshooting
- Starter trips overload relay on star-to-delta transition
- Cause: Motor has not reached sufficient speed before timer initiates transition; load too heavy for star torque Fix: Increase the timer delay setting to allow longer acceleration time in star. If the motor cannot reach speed under load in star, the load may be too heavy for star-delta starting — consider a soft starter instead.
- Delta contactor KM2 will not energise after timer expires
- Cause: KM3 auxiliary interlock NC contact not opening (KM3 coil not de-energising), or timer contact not closing Fix: Verify KM3 de-energises on timer expiry. Check KM3 NC auxiliary contact continuity with power off. Verify timer output contact type (NO timed) and wiring.
- Motor runs in star only (no transition to delta)
- Cause: Timer not energised, timer set point too long, or delta contactor coil circuit open Fix: Verify timer coil is energised from start. Check timer delay setting. Test KM2 coil circuit continuity. Verify KM3 NC auxiliary interlock is in correct position in the KM2 coil circuit.
Frequently asked questions
Why does a star-delta starter reduce starting current?
In star connection, each motor winding receives only 1/√3 (approximately 58%) of the line voltage. Since current is proportional to voltage (for a given winding impedance), the winding current — and therefore the supply current — is reduced to approximately one-third of the direct-on-line starting current.
What is the typical timer setting for the star-to-delta transition?
The timer delay is set to match the time required for the motor to reach near-synchronous speed in star configuration — typically 6 to 15 seconds. The correct setting depends on the motor's rated speed, load inertia, and load torque characteristics. Setting it too short causes a current spike from transitioning before the motor reaches speed.
Why must the star and delta contactors be interlocked?
If both the star and delta contactors were to close simultaneously, the motor winding ends in the star contactor would be shorted to the phase conductors connected through the delta contactor, creating a phase-to-phase short circuit with potentially catastrophic fault current. Both electrical (auxiliary contact interlocking) and mechanical interlocking are required.
Can any 3-phase motor be started with a star-delta starter?
No. The motor must have all six winding terminals accessible (U1, V1, W1, U2, V2, W2) and must be rated for delta connection at the supply voltage. A motor rated only for star connection at the supply voltage cannot be run in delta — its windings would be overvoltaged.
What happens if the motor is loaded too heavily during the star phase?
If load torque is too high during the star phase, the motor may not accelerate to sufficient speed before the timer initiates the delta transition. This causes a high current transient on transition — sometimes higher than DOL starting current — and may trip the overload relay. The load must be within the starter's torque capability.
Related diagrams
- star delta starter control circuit diagram with timer
- star delta control diagram with timer
- automatic star delta starter control circuit diagram
- control circuit of star delta starter
- control wiring of star delta starter
- star delta starter control circuit diagram