Control Wiring of Star Delta Starter: Timer, Contactor Sequence, and Circuit Diagram
This is a free printable control wiring of star delta starter: download the diagram as SVG or open it and print to paper or PDF.
Control wiring of a star delta starter uses three contactors and a timer relay to start a three-phase motor in star, then switch to delta after a timed delay, reducing starting current.
A star-delta (Y-Δ) starter is one of the most widely used reduced-voltage starting methods for three-phase squirrel-cage induction motors. By initially connecting the motor windings in star configuration, the voltage applied across each winding is reduced to 1/√3 (approximately 58%) of the supply voltage, reducing starting current to approximately one-third of the direct-on-line starting current. After a timer-controlled delay, the motor transitions to delta connection for full-voltage running.
The power circuit uses three contactors: the main contactor (KM1), the star contactor (KM3), and the delta contactor (KM2). At start, KM1 (main) and KM3 (star) close simultaneously, connecting the motor in star. The winding end terminals (U2, V2, W2) are shorted together by the star contactor, creating the star point. After the timing period — typically 5–15 seconds depending on motor and load — the timer relay opens KM3 (star) and closes KM2 (delta), completing the winding connections in delta.
The control circuit is the more complex element. Its critical requirement is that the star and delta contactors can never be energised simultaneously, as this would short-circuit two supply phases through the motor windings. Electrical and mechanical interlocking between KM2 and KM3 is mandatory. Electrical interlock uses normally-closed auxiliary contacts of each contactor in series with the other's coil: KM3's NC auxiliary contact sits in the KM2 coil circuit, and KM2's NC auxiliary contact sits in the KM3 coil circuit. Mechanical interlock is achieved by fitting an interlock module between the two contactor bodies.
The timer relay (typically an on-delay type) begins timing when KM1 is energised. When the timer expires, it changes state: its normally-closed contact in the star contactor circuit opens (de-energising KM3), and after a brief interval, its normally-open contact in the delta circuit closes (energising KM2). The brief interval between star opening and delta closing is critical — simultaneous transition causes a current spike; some control schemes use a transition relay to enforce the gap.
The control circuit also includes an overload relay (F1) in series with the main contactor coil circuit, and a stop pushbutton (NC) and start pushbutton (NO) in the standard latching arrangement.
How to wire control wiring of star delta starter
- Understand the power circuit In the power circuit, the main contactor (KM1) connects supply L1, L2, L3 to motor terminals U1, V1, W1. The star contactor (KM3) shorts motor terminals U2, V2, W2 together (forming the star point). The delta contactor (KM2) connects U2 to V1, V2 to W1, and W2 to U1 — creating the delta cross-connections. KM2 and KM3 operate on mutually exclusive motor winding end-terminal connections.
- Wire the main contactor Connect three-phase supply (L1, L2, L3) through the overload relay to the three input terminals of KM1. Connect the three output terminals of KM1 to motor terminals U1, V1, W1. Run a separate set of conductors from U1, V1, W1 to the respective input terminals of the delta contactor KM2 and to one side of the star contactor KM3.
- Wire the star contactor Connect the three output terminals of KM3 together (link them) to form the star point, or connect all three to the same bus link. KM3's input terminals connect to motor terminals U2, V2, W2.
- Wire the delta contactor Connect KM2 to cross-connect motor winding ends to starts: U2 to the V1 supply connection, V2 to the W1 supply connection, W2 to the U1 supply connection. Verify this against the specific power circuit diagram for the motor and starter.
- Wire the control circuit Wire from one phase of the control supply through: the stop button (NC) → start button (NO) → overload relay NC auxiliary contact → to KM1 coil. Add KM1 NC auxiliary in series with timer coil if required. Add a hold-in contact (KM1 NO auxiliary) in parallel with the start button.
- Wire the timer and interlocks Connect the timer relay (on-delay) coil to energise with KM1. Connect the timer NC contact in series with the KM3 coil (so KM3 de-energises when the timer expires). Connect the timer NO contact in series with KM2 coil (so KM2 energises after the timer expires). Add the electrical interlocks: KM3 NC auxiliary in series with KM2 coil; KM2 NC auxiliary in series with KM3 coil.
- Commission and set the timer With the installation complete and checked, energise the circuit at reduced load if possible. Set the timer delay to a value that allows the motor to reach near-synchronous speed in star — typically 5–15 seconds. Monitor the motor current during start with a clamp meter to verify the star-delta transition produces a smooth current profile.
Specifications
| Starting current reduction vs DOL | Reduced to approximately 1/3 of DOL starting current |
|---|---|
| Starting torque reduction vs DOL | Reduced to approximately 1/3 of DOL starting torque |
| Applied winding voltage (star) | Supply line voltage / √3 (approximately 58% of line voltage) |
| Typical timer setting range | 5–15 seconds (application-dependent) |
| Contactor duty category | AC-3 (squirrel-cage motor starting) |
| Interlock type required | Both mechanical AND electrical interlock between KM2 and KM3 |
| Overload relay location | Main contactor (KM1) branch, measuring line current |
| Applicable standard | IEC 60947-4-1 (contactors and starters) |
Safety warnings
- Star-delta starter installation must be carried out by a licensed or registered electrician in accordance with applicable wiring regulations (IEC 60364, BS 7671, NEC/NFPA 70, AS/NZS 3000). These diagrams are illustrative reference material only.
- Always isolate the main incoming supply, lock out and tag out (LOTO), and verify all conductors are dead before working on any contactor terminal, busbar, or wiring in the starter panel.
- Both mechanical and electrical interlocking between KM2 (delta) and KM3 (star) contactors are mandatory safety requirements, not optional enhancements. Operating without both interlock methods risks a phase-to-phase short circuit.
- The overload relay must be set to the motor's nameplate full-load current. Do not upsize to prevent trips — investigate the cause of tripping.
- During star-delta transition, the motor is momentarily disconnected from the supply. Ensure the driven load's inertia and the transition timing are correctly matched to avoid load runaway or current transients that could damage the starter.
Tools needed
- Approved voltage tester (two-pole)
- Clamp meter (for measuring starting and running current)
- Screwdrivers (flat, insulated, torque-controlled)
- Multimeter (for control circuit verification)
- Wire stripper and ferrule crimping tool
- Stopwatch or timer (for setting and verifying timer relay)
- Label printer (for circuit labelling)
Common mistakes
- Omitting the mechanical interlock between KM2 and KM3, relying solely on electrical interlocks — a welded contact on one contactor can defeat electrical interlock alone.
- Incorrectly wiring the delta cross-connections, causing the motor to run in the wrong direction in delta, or producing unbalanced phase voltages.
- Setting the timer too short so the motor has not accelerated sufficiently before delta transition, causing a current spike as severe as a DOL start.
- Connecting the overload relay in the star contactor branch only, meaning the relay sees only the star current (which is 1/√3 of line current) — the relay must be in the main contactor branch to see full line current.
- Not fitting a control transformer, causing the control circuit to operate at full line voltage — requiring all control wiring and devices to be rated accordingly and increasing shock risk during maintenance.
Troubleshooting
- Motor starts in star but does not transition to delta; stops after timer expires
- Cause: Timer wired to de-energise KM3 (correct) but no separate path to energise KM2, or electrical interlock preventing KM2 from closing Fix: Trace the KM2 coil circuit: verify the timer NO contact is wiring to energise KM2 after expiry. Check KM3 NC auxiliary contact is released (KM3 de-energised) before KM2 can close.
- Overload relay trips during star-to-delta transition
- Cause: Transition current spike too high; timer period too short; motor not at speed before transition Fix: Increase timer delay by 2–5 second increments. Monitor transition current with a clamp meter. If transition current remains high, check driven load for mechanical resistance.
- Motor runs in wrong direction in delta after running correctly in star
- Cause: Delta cross-connection wiring error: winding ends not cross-connected to the correct winding starts Fix: Isolate and verify the delta contactor wiring: U2 → V1, V2 → W1, W2 → U1 (or per the specific motor and starter diagram). Correct any transposed connections.
Frequently asked questions
Why is a star-delta starter used instead of a direct-on-line starter?
A DOL starter applies full voltage to the motor immediately, producing starting currents of 6–8 times the full-load current. This creates a voltage dip on the supply network and mechanical shock to the driven load. A star-delta starter reduces starting current to approximately one-third of DOL starting current, reducing supply disturbance and mechanical stress, at the cost of also reducing starting torque to one-third.
What is the timing delay between star and delta changeover?
The delay varies by application and is set on the timer relay. A typical setting is 5–15 seconds, chosen to allow the motor to accelerate to near-synchronous speed in star before switching to delta. If the timer is set too short, the motor has not accelerated sufficiently and the transition to delta causes a high current spike — effectively similar to a DOL start at the moment of switching.
What happens if the star and delta contactors close simultaneously?
Simultaneous closure of KM3 (star) and KM2 (delta) creates a short circuit across the supply phases through the motor winding terminals, causing immediate high fault current. This will trip the overcurrent protection but may also damage the contactors, motor windings, and supply cables. This is why both electrical interlocking (NC auxiliary contacts) and mechanical interlocking are mandatory.
Why does a star-delta starter not suit all motor loads?
In star, the motor produces only one-third of its DOL starting torque. If the load requires a high starting torque (conveyor belt under full load, loaded compressor), the motor may not accelerate sufficiently during the star period and will stall or fail to reach transition speed. Star-delta starting is best suited to low-starting-torque applications such as centrifugal fans and pumps starting against open discharge.
What is the role of the timer relay in a star-delta starter?
The timer relay (typically an on-delay relay) begins timing when the main contactor KM1 is energised. After the set delay expires, the timer changes state its output contacts. The normally-closed timer contact in the star contactor circuit opens (releasing KM3), and the normally-open timer contact in the delta circuit closes (energising KM2), completing the star-to-delta transition.
Related diagrams
- control circuit of star delta starter
- automatic star delta starter control circuit diagram
- power diagram of star delta starter
- star delta starter control circuit diagram
- star delta starter control circuit diagram with timer
- star delta starter control diagram with timer