SF6 Circuit Breaker Diagram

Sf6 Circuit Breaker Diagram — circuit diagram showing component connectionsMain MCB 63ABreaker 1 - 20ABreaker 2 - 15ABreaker 3 - 20AKitchen OutletsLightingGeneral OutletsEarth Bus230V AC UtilityDistribution Panel / DB BoardMain MCB feeds individual circuit breakers
SF6 Circuit Breaker Diagram — interactive diagram. Open it in the editor to customise components and wiring.

This is a free printable sf6 circuit breaker diagram: download the diagram as SVG or open it and print to paper or PDF.

An SF6 circuit breaker uses sulphur hexafluoride gas under pressure to quench the arc formed when high-voltage contacts separate, enabling interruption at transmission and sub-transmission voltages.

Sulphur hexafluoride (SF6) is an electronegative gas with an arc-quenching capability roughly 100 times greater than air at equivalent pressure. This property makes it the dominant insulating and interrupting medium in high-voltage circuit breakers rated from 11 kV up to 1 200 kV at transmission level.

A typical SF6 circuit breaker diagram shows three primary assemblies: the interrupter unit (sometimes called the arc-quenching chamber), the operating mechanism, and the gas monitoring system. Inside the interrupter unit, fixed and moving contacts are enclosed in a hermetically sealed vessel filled with SF6 at a gauge pressure typically between 0.5 MPa and 0.7 MPa (5 to 7 bar) for medium-voltage switchgear, and higher for transmission-class equipment.

When the breaker opens under fault conditions, the moving contact withdraws. The arc formed between the separating contacts is blasted with SF6 gas directed through a nozzle — either by a puffer piston driven by the operating mechanism, or by the thermal expansion of the arc itself in self-blast designs. The electronegative SF6 molecules rapidly capture free electrons from the plasma, extinguishing the arc at or very near the natural current zero crossing.

The operating mechanism is typically a spring-stored energy type, which charges a closing spring via an electric motor. Trip operations are initiated by the release of a separate trip latch, using power from a DC battery-backed control supply.

SF6 is a potent greenhouse gas (GWP approximately 23 500 over a 100-year horizon, per IPCC AR6). Modern regulations in many jurisdictions — including the EU F-Gas Regulation — increasingly restrict its use and mandate leak detection systems. Gas density monitors (not pressure gauges, since gas density varies with temperature) alarm at two set points: a lower alarm level for maintenance and a lockout level that prevents operation to protect the interrupter.

All SF6 equipment diagrams should include the gas density monitor connections, operating mechanism control circuit (closing coil CC, tripping coil TC1 and TC2 in dual-coil designs), anti-pumping relay (Y), and auxiliary contacts for SCADA and protection relay feedback.

How to wire sf6 circuit breaker diagram

  1. Identify main components on the diagram Locate the interrupter chamber (arcing contacts and main contacts), the puffer cylinder or self-blast expansion volume, the operating mechanism housing, and the gas density monitor with its two-level output contacts.
  2. Trace the control circuit Follow the DC control supply from the battery through the closing coil (CC) and tripping coil(s) (TC1, TC2). Identify the anti-pumping relay (Y) wired in parallel with the closing coil to prevent multiple close operations while the trip signal persists.
  3. Identify auxiliary and alarm contacts Locate the 'b' (normally open) and 'a' (normally closed) auxiliary contacts from the main mechanism. These feed the SCADA system, protection relay binary inputs, and local indication. The gas density monitor alarm and lockout contacts are typically wired to the station alarm system and trip circuit respectively.
  4. Understand the spring-charge motor circuit The closing spring motor is energised automatically after each close operation to re-charge the spring. On the diagram, trace the motor supply from the AC or DC auxiliary bus through the spring-discharged limit switch and the anti-pumping relay contacts.
  5. Check interlock and permissive connections In GIS installations, isolator position contacts are interlocked with the breaker control circuit to prevent operation unless isolators are in correct states. Confirm earthing switch position contacts are included in the permissive chain.
  6. Verify current transformer and protection relay connections Current transformers (CTs) mounted on the interrupter bushing feed the differential and overcurrent protection relays. Confirm that CT secondary circuits are correctly earthed at one point, and that the relay trip output is wired to the correct tripping coil terminal.

Specifications

Rated voltage range11 kV to 1 200 kV (voltage class dependent)
SF6 filling pressure (medium voltage, gauge)Typically 0.5 MPa to 0.7 MPa at 20 °C
Arc-quenching relative capability vs airApproximately 100× at equivalent pressure
SF6 global warming potential (GWP, 100yr)Approximately 23 500 (IPCC AR6)
Typical rated short-circuit breaking current16 kA to 63 kA (application dependent)
DC control supply voltage (common)48 V DC, 110 V DC, or 220 V DC
Closing spring re-charge time (typical)10 seconds to 30 seconds after close operation
Operating temperature range (standard)–25 °C to +55 °C per IEC 62271-100

Safety warnings

Tools needed

Common mistakes

Troubleshooting

Gas density monitor showing alarm level
Cause: SF6 leak in the interrupter chamber, gas piping, or monitor connection; or monitor calibration drift Fix: Use an SF6 leak detector to locate the source. If no leak is found, have the density monitor recalibrated. Do not top up with gas without first establishing the cause and rate of leakage.
Breaker fails to close on command
Cause: Closing coil not energised (control supply fault, anti-pumping relay locked, spring not charged); or mechanical fault in closing latch Fix: Check DC control voltage at the closing coil terminals. Verify the spring-charge motor has completed its cycle (spring-charged limit switch closed). Check the anti-pumping relay has reset after the previous operation.
High contact resistance measured across main terminals
Cause: Main contact wear, silver contact oxide, or misalignment after long-term operation Fix: Measure contact resistance with a micro-ohmmeter. Compare against manufacturer's acceptance limits (typically < 50 µΩ for transmission-class units, though this varies widely by rating). Excessive resistance requires internal inspection and possible contact replacement by authorised personnel.

Frequently asked questions

Why is SF6 used in high-voltage circuit breakers instead of air or oil?

SF6 has approximately 100 times the dielectric strength of air and exceptional arc-quenching ability due to its electronegativity. This allows breakers to interrupt very large fault currents in a much smaller physical volume than equivalent air-blast or oil-filled designs, which is critical in compact GIS (gas-insulated switchgear) substations.

What is the function of the gas density monitor in an SF6 breaker?

A gas density monitor measures SF6 density (not raw pressure) to compensate for temperature variation. It provides two alarm levels: a first level triggers a maintenance alert, and a second lower level initiates a lockout that prevents the breaker from being operated, protecting the interrupter from arc damage in low-SF6 conditions.

What is the difference between a puffer-type and self-blast SF6 breaker?

A puffer breaker uses a mechanical piston driven by the operating mechanism to force SF6 through the arc nozzle. A self-blast (or thermal-blast) breaker relies on the heating of gas by the arc itself to build pressure in an expansion volume, supplemented by a puffer for low-current interruptions where arc energy is insufficient.

Can SF6 circuit breakers interrupt DC fault currents?

Standard SF6 breakers are designed for AC interruption, exploiting the natural current zero crossing. DC interruption requires different technology (such as hybrid designs with artificial current zero creation) and SF6 alone is not used for high-voltage DC circuit breaking without significant additional circuitry.

What are the environmental concerns with SF6 in switchgear?

SF6 has a global warming potential of approximately 23 500 times that of CO2 over 100 years and persists in the atmosphere for over 3 000 years. Many jurisdictions now mandate gas handling procedures, leak-detection monitoring, and recovery before decommissioning. Alternative gases (such as fluoronitrile blends) are being introduced, though SF6 remains dominant at high voltage levels.

Related diagrams

Free electrical calculators

Edit this diagram free in the online editor