Wye-Delta (Star-Delta) Motor Starting Diagram

Wye Delta Diagram — circuit diagram showing component connections3-Phase SupplyFuse 63AKMain Contactor KM1KStar Contactor KM2KDelta Contactor KM3Overload RelayM3~Motor M1230V AC UtilityStar-Delta Motor StarterStar for start, delta for runOL relay protects motor
Wye-Delta (Star-Delta) Motor Starting Diagram — interactive diagram. Open it in the editor to customise components and wiring.

This is a free printable wye delta diagram: download the diagram as SVG or open it and print to paper or PDF.

A wye-delta diagram shows how a three-phase induction motor is started in star (wye) configuration then switched to delta, reducing inrush current to roughly one-third of direct-on-line starting current.

Wye-delta starting, also called star-delta starting in IEC countries, is one of the oldest and most widely used reduced-voltage starting methods for three-phase squirrel-cage induction motors. The technique exploits a fundamental property of three-phase systems: when motor windings are connected in star (wye), each winding receives only 57.7% of line voltage (line voltage divided by the square root of 3). Because torque is proportional to the square of voltage, starting torque in star is one-third of what it would be in delta. More importantly for the supply network, starting current is also reduced to one-third of delta starting current.

The diagram typically shows three main contactors: the main contactor (KM1) that connects the motor to the supply throughout operation, the star contactor (KM2) that short-circuits the motor neutral point during starting, and the delta contactor (KM3) that reconnects the windings in delta for normal running. A timer relay (typically 5–15 seconds, set to suit load inertia) triggers the transition from star to delta once the motor has accelerated to approximately 70–80% of synchronous speed.

Mechanical and electrical interlocking between KM2 and KM3 is mandatory: closing both simultaneously short-circuits two phases of the supply and will destroy the contactors and potentially cause injury. Most modern designs use both a mechanical interlock (a lever linkage between contactor bodies) and an electrical interlock (normally-closed auxiliary contacts wired in series with the opposing coil circuit).

The main variants are open-transition and closed-transition. Open-transition (the standard wye-delta circuit) briefly disconnects the motor from the supply during changeover, causing a transient current spike that can exceed direct-on-line inrush for a few milliseconds. Closed-transition inserts resistors or an impedance during changeover to prevent this spike, and is preferred for sensitive loads or large motors. Wye-delta starting is suitable for motors where the connected load allows starting under light or no load, because starting torque at one-third means heavily loaded conveyors or compressors may not start successfully.

How to wire wye delta diagram

  1. Confirm motor winding configuration Verify the motor nameplate shows both star and delta voltage ratings (e.g., 400V/690V or 230V/400V). The delta voltage rating must match your supply voltage. All six winding terminals (U1, V1, W1, U2, V2, W2) must be accessible on the terminal board — motors with only three terminals cannot be wye-delta started.
  2. Size the contactors and overload relay The main contactor (KM1) carries full line current and is rated at 100% of motor full-load current (FLC). The star contactor (KM2) carries winding current, which is FLC divided by the square root of 3, so it can be rated at 58% FLC. The delta contactor (KM3) also carries 58% FLC. The overload relay is set to motor FLC and installed in the main circuit, not the star or delta branch.
  3. Wire the main contactor to the supply and motor terminals U1, V1, W1 Connect the three supply phases (L1, L2, L3) through the main contactor KM1 to motor terminals U1, V1, W1 respectively. Route this wiring through the overload relay thermal elements. The overload relay output feeds KM1 coil control circuit.
  4. Wire the star contactor to short-circuit the neutral point Connect the star contactor KM2 across motor terminals U2, V2, W2. When KM2 closes, it joins these three terminals together, forming the star neutral point. Install a mechanical interlock and wire normally-closed auxiliary contact of KM3 in series with the KM2 coil to prevent simultaneous closure with the delta contactor.
  5. Wire the delta contactor to reconnect windings in delta The delta contactor KM3 connects U2 to V1, V2 to W1, and W2 to U1 (the exact cross-connection depends on the manufacturer's wiring diagram for the motor terminal labelling convention). Install mechanical and electrical interlocks with KM2. Wire a normally-closed auxiliary of KM2 in series with the KM3 coil circuit.
  6. Connect and set the timer relay Wire the on-delay timer relay coil in parallel with the main contactor KM1 coil (so timing starts when the motor starts). The normally-open timed contact de-energises KM2 and energises KM3 after the set delay. Adjust the timer using a clamp ammeter: the motor should have stabilised in speed before switching; a sharp current transient at changeover indicates the motor has not yet accelerated sufficiently.
  7. Test, commission, and verify interlock operation Before energising with the motor connected, verify the mechanical interlock prevents KM2 and KM3 closing simultaneously by attempting to close them by hand. Energise and confirm sequence: KM1 and KM2 close first (star start), then KM2 opens and KM3 closes (delta run) at timer expiry. Check overload relay trip current with a clamp meter under full load.

Specifications

Starting current (line) vs DOLApproximately 33% of direct-on-line starting current
Starting torque vs DOLApproximately 33% of full delta (DOL) starting torque
Star phase voltage (400 V system)230.9 V (400 V ÷ √3)
Typical timer range5–15 seconds (adjusted to suit motor and load inertia)
Minimum motor terminal accessibilitySix individual terminals (U1, V1, W1, U2, V2, W2)
Applicable motor typesThree-phase squirrel-cage induction motors only
Recommended transition type for motors above 55 kWClosed-transition (with transition resistors) to limit re-acceleration transient
Relevant standardsIEC 60947-4-1 (contactors), IEC 60034-1 (motors), NEC Article 430 (US)

Safety warnings

Tools needed

Common mistakes

Troubleshooting

Overload relay trips every time during the star-to-delta transition
Cause: Timer set too short; motor has not accelerated sufficiently before switching, causing a large transient current spike Fix: Increase the timer delay in 1–2 second increments while monitoring the current waveform with a clamp meter until the transition transient is minimised. Also verify overload relay class setting (Class 10 or 20) is appropriate for the motor.
Motor hums and fails to accelerate past star speed even after the timer expires
Cause: Load torque exceeds available star starting torque, or the delta contactor is failing to close Fix: Check the delta contactor coil voltage and auxiliary contact continuity. If the contactor operates correctly, the load may be too heavy for wye-delta starting and a different starting method (soft starter or VFD) should be considered.
Contactors chatter or arc excessively during star-to-delta changeover
Cause: Open-transition switching; brief disconnection causes voltage transient as motor EMF and supply re-synchronise out of phase Fix: Measure the transition using a power analyser. If current spikes are excessive, consider converting to a closed-transition circuit with transition resistors, or use an electronic soft starter instead.
Motor runs hot in the star configuration during starting
Cause: Timer set too long, keeping the motor in star at reduced torque while the load demands more current than the star winding can efficiently supply Fix: Shorten the timer delay so the transition to delta happens once the motor has reached approximately 70–80% of synchronous speed. Check the motor nameplate for the duty cycle and starting frequency limits.
Star contactor and delta contactor both show burn marks on the contacts
Cause: Interlock failure — both contactors closed simultaneously, creating a phase short circuit Fix: Replace both contactors. Inspect and restore the mechanical interlock linkage. Verify normally-closed auxiliary contacts of each contactor are wired in series with the opposing coil and confirm operation before re-commissioning.

Frequently asked questions

What is the difference between wye and star connections in motor starting?

Wye and star are two names for the same connection topology where three winding ends meet at a common neutral point. IEC and European standards use 'star'; North American standards tend to use 'wye'. The electrical behaviour is identical. Both terms appear on wye-delta diagrams depending on regional convention.

Why does wye-delta starting reduce inrush current to one-third?

In star connection each winding sees line voltage divided by the square root of 3 (approximately 57.7% of line voltage). Because impedance is fixed, current is proportional to voltage. Starting current in star is therefore 57.7% of delta voltage divided by the same impedance, and since current scales with voltage, total line current is one-third of direct delta starting current.

How long should the timer be set for wye-delta starting?

Timer setting depends on motor size and driven load inertia; a typical range is 5–15 seconds. The motor should reach at least 70% of synchronous speed before switching to delta. Setting the timer too short causes a large transition transient; too long wastes time in reduced-torque mode and can overheat the motor windings.

What loads are not suitable for wye-delta starting?

Loads that require high starting torque under load are unsuitable: reciprocating compressors, heavily laden conveyors, mixers with viscous material, and ball mills. These require the full delta torque from standstill. Wye-delta is best suited to centrifugal pumps, fans, and centrifuges that start unloaded or against low initial resistance.

Is wye-delta starting still used, or have soft starters replaced it?

Both are still widely used. Wye-delta is favoured where simplicity, low cost, and maintainability matter; the components (contactors, timer, overload relay) are universally understood by electricians worldwide. Electronic soft starters and variable-frequency drives (VFDs) offer smoother ramp-up and closed-loop control, but at higher cost and greater complexity.

Related diagrams

Free electrical calculators

Edit this diagram free in the online editor