Earth Leakage Relay Symbol

Earth Leakage Relay symbolELR
The Earth Leakage Relay symbol (IEC 60617 / ANSI Y32.2).

Definition: The Earth Leakage Relay symbol represents a protective relay that monitors residual ground-fault current in an electrical installation and issues a trip signal when leakage current exceeds a set threshold, as defined in IEC 60755 and IEC 60947-2, with the designator K (relay) or RCD on schematic diagrams.

Also known as: ground fault relay, RCD relay, residual current relay, earth fault relay, leakage current relay, ground leakage relay.

What the Earth Leakage Relay symbol means

The Earth Leakage Relay symbol denotes a sensing and switching device that continuously measures the vector sum of all line and neutral currents through a toroidal current transformer; any imbalance (ground fault or leakage current) above the set trip level — typically 30 mA for personnel protection or 100–500 mA for equipment protection — causes the relay to energise a trip coil or open a circuit breaker.

On industrial and electrical schematics, this symbol appears in the protective-relay circuit alongside a current transformer (CT) on the supply cable and a trip contact wired in series with the circuit-breaker shunt-trip or contactor coil. The relay plays a critical safety role in preventing electric shock and electrical fires caused by insulation breakdown.

How to identify the Earth Leakage Relay symbol

The earth leakage relay symbol is drawn as a rectangle (the standard relay block convention) with the label 'ELR', 'RCD', or a delta/residual-current symbol (sometimes ΔI) inside. Three pins are shown: Line input (L, left side), a +24 V or auxiliary supply (VCC, top), and a Trip output (right side) connected to a downstream protective device. The symbol may also show a toroidal CT around the monitored conductors, with a dashed line linking the CT secondary to the relay block.

Function in a circuit

The earth leakage relay measures residual current — the algebraic sum of instantaneous current values in the phase and neutral conductors — using a toroidal core current transformer. Under normal conditions the sum is zero; a leakage path to earth creates an imbalance that the relay detects. When the imbalance exceeds the set threshold (Idn), the relay output activates a trip signal on the Trip pin, opening the upstream breaker or contactor within the specified operating time (typically <300 ms for 30 mA personnel-protection types per IEC 61008).

Standards: IEC vs ANSI

IEC 60617IEC 60755 defines general requirements for residual current-operated protective devices; IEC 60947-2 Annex B covers residual current devices integrated with circuit breakers. The relay block symbol follows IEC 60617 group 07 (switching devices) with a residual-current designator. Trip thresholds and response times are defined in IEC 61008 (RCCBs) and IEC 61009 (RCBOs).
ANSI/IEEE 315ANSI/IEEE C37.2 device function number 64 is assigned to ground-detector relays; ground-fault protection for personnel (GFPE) is governed by NFPA 70 (NEC) Article 230.95 and UL 943. The ANSI relay block symbol is a rectangle with the function number '64' inside.
Key differenceIEC designates the function with a residual-current symbol (ΔI) and uses device codes from IEC 60947-2; ANSI/IEEE uses device function number 64 inside the relay rectangle. Physical trip thresholds and test requirements also differ: IEC 61008 type A/AC vs. ANSI/UL 943 Class A (6 mA body-current threshold for personnel protection).

Terminals / pins

PinName
lLine
tripTrip
vcc+24V

Typical values

Trip current (Idn): 10 mA, 30 mA (personnel protection), 100 mA, 300 mA, 500 mA (equipment/fire protection). Auxiliary supply: typically 24 V DC or 110–230 V AC. Trip time: ≤300 ms at Idn, ≤40 ms at 5×Idn per IEC 61008.

Where the Earth Leakage Relay symbol is used

Example

In a 3-phase motor-control circuit, an earth leakage relay with a 100 mA trip threshold is connected to a toroidal CT clamped around the three phase conductors and neutral of the motor cable. Under normal operation the CT measures zero residual current. When a phase winding develops an insulation fault to the motor frame, the leakage current through the protective-earth conductor unbalances the CT, and the relay triggers the trip output, disconnecting the contactor feeding the motor within 150 ms.

Key facts

Frequently asked questions

What does the earth leakage relay symbol mean in a circuit diagram?

The earth leakage relay symbol marks a protective device that monitors the residual (leakage) current in a circuit and opens the circuit when leakage exceeds a set threshold (e.g. 30 mA). It is drawn as a relay rectangle labelled 'ELR' or 'RCD' with Line, Trip, and auxiliary supply pins.

What is the difference between an earth leakage relay and an RCD?

An RCD (residual current device) is a self-contained switch/relay unit that both detects leakage current and interrupts the circuit. An earth leakage relay is only the sensing/tripping relay; it detects the fault and sends a trip signal to a separate circuit breaker or contactor. Both are governed by IEC 60755 and IEC 60947-2.

What trip current level does an earth leakage relay use for personnel protection?

For personnel shock protection the standard trip threshold is 30 mA per IEC 61008 and IEC 60364-4-41. At this level the relay must operate within 300 ms at the rated Idn current. Higher thresholds (100–500 mA) are used for equipment and fire protection where personnel contact is not the primary concern.

What is the ANSI device function number for an earth leakage relay?

ANSI/IEEE C37.2 assigns device function number 64 to ground-detector relays. On one-line diagrams the relay block is labelled '64' inside a rectangle. IEC schematics instead use a residual-current block symbol with the ΔI designation.

What does the Trip pin on the earth leakage relay symbol do?

The Trip pin carries the relay output signal that activates a shunt-trip coil, contactor de-energisation coil, or alarm when leakage current exceeds the set threshold. In the symbol, the Trip pin (x=50, y=20) connects to the downstream protective device to open the faulty circuit.

Why does an EV charger require a Type B earth leakage relay?

EV chargers can produce smooth DC leakage currents from their power electronics. Type A residual current devices only detect AC and pulsating DC faults and will not respond to smooth DC leakage. IEC 61009 and IEC 60364-7-722 therefore require Type B devices (sensitive to AC, pulsating DC, and smooth DC) for EV charging installations.

How does the earth leakage relay symbol differ from a standard overcurrent relay symbol?

An overcurrent relay symbol (ANSI function 51) responds to excessive load current flowing in the normal circuit path and uses a current transformer in series with the line. An earth leakage relay symbol includes a toroidal CT enclosing all conductors and responds only to residual (imbalance) current that bypasses the load via an earth path.

Place the Earth Leakage Relay symbol on a wiring diagram or schematic in the free online circuit diagram maker — no download required.