DOL Starter Wiring Diagram: Direct-On-Line Motor Starter Explained

Direct-on-line (DOL) starting connects a three-phase motor directly across the supply at full voltage. It is the simplest motor starting method -- no reduced voltage, no autotransformer, no timing gymnastics. The motor sees full line voltage the moment the contactor closes, draws its full locked-rotor current (typically 6 to 8 times FLC), and accelerates to rated speed. For motors up to 7.5 kW (10 HP) on most utility supplies, DOL starting is the standard approach.

This guide covers the complete power circuit and control circuit of a DOL starter -- contactor sizing, overload relay setup, start/stop pushbutton wiring, and the holding (seal-in) contact that keeps the motor running after you release the start button.

How a DOL Starter Works

A DOL starter has two separate circuits that need to be understood independently before looking at the combined diagram.

Power circuit: Carries the full motor current. Three-phase supply (L1, L2, L3) flows through the main contactor and then through the overload relay thermal elements to the motor terminals (U, V, W).

Control circuit: Carries a small current -- typically 1 to 5A -- that operates the contactor coil. The control voltage can be the same as the supply (e.g., 400V across two phases) or stepped down via a control transformer to 110V or 24V for safety.

Key Components

Power Circuit Wiring

The power circuit is straightforward. Follow this connection sequence:

  1. Three-phase supply enters through an isolator or main circuit breaker (MCCB) -- size this at 125% of motor FLC per NEC 430.52, or use a Type D MCB rated for motor starting.
  2. Incoming phases L1, L2, L3 connect to the top (line) terminals of the main contactor KM.
  3. Bottom (load) terminals of KM connect to the input terminals of the overload relay (T1, T2, T3 or 2, 4, 6 depending on manufacturer).
  4. Output terminals of the overload relay connect to motor terminals U, V, W.
  5. Motor frame must be bonded to earth (ground) at the motor terminal box.

Safety note: The power circuit carries full motor current at line voltage. Use cables sized to 125% of motor FLC. For a 5.5 kW motor at 400V (FLC approximately 11A), use 2.5 mm² copper minimum. Always isolate and verify dead before working on the power circuit.

Contactor Sizing

Contactors are rated by AC utilization category. Motor loads require AC3 rating (squirrel cage motors, starting and plugging). For a 5.5 kW / 400V motor with 11A FLC, a 16A AC3 contactor is the minimum -- common choices are Schneider LC1D09 (9A AC3) for smaller motors and LC1D18 (18A AC3) for this range.

Overload relay setting: Set the overload to 100% of motor FLC (not 125%). The overload relay is a slow-trip device designed to trip on prolonged overcurrent, not on normal starting inrush. Set it at nameplate amps.

Control Circuit Wiring

This is where the DOL starter gets interesting. The control circuit must latch (hold) after the start button is released, and it must unlatch when the stop button is pressed or the overload trips.

Schematic -- top to bottom

Control supply (L1 or 110V)
       |
    [S1 NC Stop]
       |
    [F1 NC Overload]
       |
    [S2 NO Start] --- parallel with [KM NO holding contact]
       |
    [KM Coil]
       |
   Neutral / L2

Wiring Step-by-Step

  1. Take the control supply from phase L1 (or the secondary of a control transformer).
  2. Run through the stop button S1 (NC terminal). The wire continues when S1 is not pressed.
  3. Continue through the overload relay NC contact (terminals 95 and 96 on most Telemecanique/Schneider overloads, or 97-98 for manual reset).
  4. Now split into two parallel paths:
    • The start button S2 (NO terminals) -- momentary path
    • The holding contact (auxiliary NO contact on KM) -- latching path
  5. Both paths rejoin and feed the KM coil terminals A1 (+) and A2 (−/neutral).
  6. Complete the circuit back to neutral or L2.

How the Seal-in Works

When you press S2, current flows through S2 and energizes the KM coil. KM pulls in and three things happen simultaneously:

The contactor stays latched until the stop button breaks the series path, or the overload relay trips its NC contact open.

NO and NC Contact Assignments

Understanding which contacts are NO and NC is critical for correct wiring.

Contact Type Normal State Function
KM main contacts NO Open Connects motor to supply when energized
KM auxiliary (holding) NO Open Seals in the start command
F1 control contact NC Closed Opens on overload trip to stop motor
Stop button S1 NC Closed Pressing opens the circuit
Start button S2 NO Open Pressing momentarily closes the circuit

Indicator Lamps (Optional)

Many panels add indicator lamps to the control circuit:

Lamp voltage must match control voltage. Use LED panel lamps for long life -- 22 mm panel-mount types (e.g., Schneider XB5AV or equivalent).

Reversing Starter (Extension of DOL)

A reversing DOL starter uses two contactors -- Forward (KM1) and Reverse (KM2) -- wired so that two supply phases are swapped when the reverse contactor is energized (swapping any two of L1/L2/L3 reverses a three-phase motor).

Interlocking is mandatory: The NC auxiliary of KM1 goes in series with the KM2 coil, and vice versa. Energizing both simultaneously causes a three-phase short circuit.

Common DOL Starter Wiring Mistakes

Testing a DOL Starter with a Multimeter

Always isolate and lock out the supply before opening the panel, then verify dead with a proven voltage tester before touching any terminal.

Testing coil continuity:

  1. Isolate the control circuit and disconnect at least one lead from the contactor coil terminals (A1/A2).
  2. Set the multimeter to the resistance (ohms) range.
  3. Measure across A1 and A2. A healthy coil reads a low-to-moderate resistance value specific to that coil's voltage rating -- check the datasheet for the expected figure.
  4. An open-circuit (infinite / OL) reading means a burned-out coil. A reading near zero ohms indicates shorted turns -- replace the coil or contactor.

Checking the overload relay trip function:

  1. With the panel isolated, locate the overload relay's TEST button (usually a small yellow or black button on the front).
  2. Set the multimeter to continuity mode and probe the NC contact terminals (typically 95-96).
  3. Press TEST -- the relay should trip, and the meter should show an open circuit.
  4. Press RESET -- continuity should return, confirming the trip mechanism and the NC contact both work correctly.

Verifying contactor contacts:

  1. With the contactor de-energized and isolated, check continuity across each main pole (L1-T1, L2-T2, L3-T3). All three should read open circuit. Any pole showing continuity while de-energized indicates welded contacts -- replace the contactor.
  2. Checking contacts in the energized (pulled-in) state involves live testing and should only be done by someone qualified to work on live panels. A healthy closed pole shows near-zero voltage drop across it.

Common DOL Starter Faults and Fixes

Symptom Likely Cause Fix
Motor hums but doesn't start Single-phasing (one phase missing) or a stuck contactor pole that isn't closing Check all three phases at the contactor's load terminals; check for a blown fuse or tripped upstream breaker on one phase
Starter trips immediately on start Overload set too low, motor stalled or jammed mechanically, or motor connections mismatched to supply voltage Confirm the OL is set to nameplate FLC, check for mechanical binding on the driven load, verify star/delta connections match the supply
Contactor chatters (buzzes, doesn't pull in fully) Low or fluctuating control voltage, or a worn coil Measure control voltage at the coil terminals under load; replace the coil if voltage is adequate but chatter continues
Motor runs but trips on overload after a while Motor mechanically overloaded, single-phasing, or OL set below actual running current Measure actual running current per phase and compare to nameplate FLC and the OL setting
Contactor drops out when the start button is released Missing or miswired holding (seal-in) contact Verify the auxiliary NO contact is wired in parallel with the start button, not in series
No control voltage at all Blown control fuse, stop button stuck open, or overload NC contact already tripped open Check the control fuse, confirm the stop button isn't stuck, confirm the overload hasn't tripped

Terminal Identification Notes

Common IEC-style numbering on contactors and overload relays -- always confirm against your specific manufacturer's datasheet, since some brands vary:

Create Your Own DOL Starter Diagram

Laying out both the power circuit and control circuit before you start panel wiring prevents expensive rework. With CircuitDiagramMaker, you can:

Create your own DOL starter diagram -- free

Key Takeaways

Dol Starter Single Line Diagram — circuit diagram showing component connectionsL1K1_outmotor_UctrlstartNPEutilityutility_nautoreturnMCB Q1Contact K1Overload F1M3~Motor M1Start S1KCoil K1230V AC UtilityDOL (Direct-On-Line) Motor StarterControl circuit (24V)
Dol Starter Single Line Diagram — open the interactive version of this diagram to customise and export it.
Direct On Line Starter Diagram — circuit diagram showing component connectionsL1K1_outmotor_UctrlstartNPEutilityutility_nautoreturnMCB Q1Contact K1Overload F1M3~Motor M1Start S1KCoil K1230V AC UtilityDOL (Direct-On-Line) Motor StarterControl circuit (24V)
Direct On Line Starter Diagram — open the interactive version of this diagram to customise and export it.
Dol Starter Circuit Diagram — circuit diagram showing component connectionsL1K1_outmotor_UctrlstartNPEutilityutility_nautoreturnMCB Q1Contact K1Overload F1M3~Motor M1Start S1KCoil K1230V AC UtilityDOL (Direct-On-Line) Motor StarterControl circuit (24V)
Dol Starter Circuit Diagram — open the interactive version of this diagram to customise and export it.

Frequently asked questions

What is the difference between a DOL starter and a star-delta starter?

A DOL starter connects the motor directly across full line voltage, drawing 6 to 8 times full load current at start. A star-delta starter reduces starting current by initially connecting the motor windings in star, then switching to delta once the motor accelerates, at the cost of extra contactors and a more complex control circuit. DOL is simpler but harsher on the supply.

Can a DOL starter be used for large motors above 10 HP?

DOL starting is generally limited to motors up to about 7.5 kW (10 HP) on typical utility supplies because the high inrush current (6 to 8x FLC) can cause unacceptable voltage dips on the supply network. Larger motors typically need a reduced-voltage method such as star-delta, a soft starter, or a VFD to limit starting current.

Is a DOL starter the same as a magnetic starter?

A magnetic starter is the general term for a contactor-based starter with overload protection -- a DOL starter is one specific type of magnetic starter, wired for full-voltage, non-reversing starting. Star-delta and reversing starters are other types of magnetic starters that use additional contactors and control logic.

What happens if the overload relay is set too high on a DOL starter?

Setting the overload above the motor's nameplate FLC delays or prevents it from tripping during a genuine overcurrent condition, which lets the motor windings overheat and can lead to insulation breakdown and premature motor failure. Always set the overload relay to 100% of nameplate FLC, not the breaker or contactor rating.

Can a DOL starter run a motor in reverse?

A standard DOL starter with a single contactor cannot reverse the motor. Reversing requires two contactors, wired so that two of the three supply phases swap when the reverse contactor energizes, along with mandatory interlocking between the two contactors to prevent them from closing simultaneously.

What is the typical starting current of a DOL-started motor?

A DOL-started motor typically draws 6 to 8 times its full-load current (FLC) for the brief moment before it accelerates to rated speed. This inrush current is why DOL starting is usually limited to smaller motors on stiff supplies -- the sudden current draw can cause noticeable voltage dips on weaker networks.

Interactive diagrams for this guide

Related guides