Timed Contact NO, Off-Delay (67-68) Symbol
Definition: The off-delay NO timed contact is a normally open contact operated by an off-delay timer: it closes immediately when the timer coil is energised and opens only after the set time has elapsed from the moment the coil is de-energised.
Also known as: off-delay NO contact, TOF contact, time-delayed opening make contact, NOTO contact, run-on contact, timer NO contact 67-68 off-delay.
What the Timed Contact NO, Off-Delay (67-68) symbol means
This symbol marks a circuit that follows its control signal on, but keeps running for a fixed time after the signal goes away, as in fan run-on. It is drawn open, with the delay arc showing that the opening (release) movement is the slow one.
How to identify the Timed Contact NO, Off-Delay (67-68) symbol
Look for a normally open contact with the semicircular delay arc linked to the blade, oriented so that the opening movement runs towards the centre of the arc (the arc faces the opposite way to an on-delay NO). It carries the timer's tag and terminals such as 67-68.
Live editor identity: Live-library identity: `off-delay-contact-no`, 40 × 60 canvas units, 2 logical terminals. Match this exact SVG and terminal list when identifying the placeable editor symbol; do not identify a physical package from the schematic outline alone.
Function and usage boundary
Energising the timer coil closes the contact at once. When the coil is de-energised the delay starts and the contact stays closed until it ends. Re-energising the coil during the delay keeps it closed and resets the timing.
Usage boundary: Use the Timed Contact NO, Off-Delay (67-68) abstraction only when the intended circuit can be expressed through these logical ports: `in` (67), `out` (68). Select a versioned physical profile and exact manufacturer datasheet before assigning package pins, ratings, or fabrication dimensions.
Standards: IEC vs ANSI
| IEC 60617 | IEC 60617 draws a timed contact as an ordinary make or break contact with the delayed-action mark (a small arc, the 'parachute') linked to the moving blade. Movement towards the centre of the arc is the delayed one, so the arc's orientation tells you whether the delay applies on operation (on-delay) or on release (off-delay). Terminal numbers follow EN 50005 practice: the function digit 5-6 marks a time-delayed break (NC) contact and 7-8 a time-delayed make (NO) contact, e.g. 55-56 and 67-68 on add-on timer blocks; single-function timer relays often use 15-16 (NC) and 15-18 (NO) for a timed changeover. |
|---|---|
| ANSI/IEEE 315 | ANSI/IEEE 315 and NEMA ICS practice draw the same function as a contact with an arrowed arc and the abbreviations TDC/TC (time delay closing) or TDO/TO (time delay opening), and label the contact with the timer's device tag (TR1, 2TR) rather than IEC function digits. |
| Key difference | Both systems mark the delayed direction on the contact itself. IEC uses the parachute arc plus EN 50005 terminal digits (55-56, 67-68); North American drawings use NOTC/NCTO-style abbreviations and the TR device tag. |
The displayed SVG is the live editor implementation, not a licensed reproduction or certification of an IEC or IEEE database glyph. Verify the exact official entry and project edition before issuing work.
Variant availability
- Editor implementation (available): This is the exact SVG and terminal geometry placed by the CircuitDiagramMaker editor.
- IEC 60617 (reference only): IEC 60617 is the official international source. This page does not present the editor SVG as a licensed or certified IEC reproduction.
- ANSI/IEEE 315 (reference only): IEEE 315 is the North American reference listed by IEEE as inactive-reserved; use the edition required by the project.
Logical terminals
The live editor exposes `in` (67), `out` (68). These are stable logical terminal IDs for diagram connectivity, not a promise that they equal physical package pin numbers.
| Logical ID | Editor terminal name |
|---|---|
| in | 67 |
| out | 68 |
Polarity and direction
This editor symbol does not encode a universal positive/negative orientation. Do not infer physical polarity or package pin numbering from left/right placement alone.
Reference designator
Project-defined: No single reference letter is asserted for this broad symbol. Apply the project standard and equipment-classification rules consistently.
Where the Timed Contact NO, Off-Delay (67-68) symbol is used
- Star-delta motor starters, where a timed contact hands over from the star to the delta contactor
- Sequential start of conveyors, pumps and fans to limit inrush current
- Run-on of extraction or cooling fans after a machine stops
- Alarm and horn circuits that must persist, or wait, for a set time
- Lubrication, purge and pre-heat steps in machine control sequences
Key facts
- Closes instantly when the timer coil is energised; opens after the set delay once the coil is de-energised.
- Shown open on the schematic (de-energised state).
- The delay arc points the opposite way to an on-delay NO contact.
- Re-energising the coil during the run-on time resets the delay.
Common interpretation mistakes
- Treating the Timed Contact NO, Off-Delay (67-68) drawing (40 × 60 canvas units) as a physical footprint. The schematic outline expresses electrical intent; package and panel dimensions come from the selected physical profile.
- Copying `in`, `out` directly to a wire marker or manufacturer package pin number. These are logical Timed Contact NO, Off-Delay (67-68) port IDs and require an exact ordered-part terminal map.
- Assuming Timed Contact NO, Off-Delay (67-68) input and output ports are interchangeable when the device or signal flow is directional.
Frequently asked questions
Does an off-delay timer need power during the delay?
Electronic off-delay relays either use a separate supply terminal or store energy internally (true off-delay). Pneumatic and mechanical off-delay blocks time out mechanically. Check the relay's datasheet: some need the supply maintained while only the control input is switched.
How is a timed contact linked to its timer?
By its device tag. The contact carries the same tag as the timer coil (for example KT1), and the cross-reference under the coil lists every contact it operates. In this editor the simulator links them the same way, so give the contact the timer's label.
What do 55-56 and 67-68 mean?
They are EN 50005 terminal numbers. The first digit is the contact's sequence number on the device; the second is the function digit, where 5-6 means a time-delayed break (NC) contact and 7-8 a time-delayed make (NO) contact. Ordinary instantaneous contacts use 1-2 (NC) and 3-4 (NO).
Sources and verification
- IEC 60617:2026 DB — Graphical symbols for diagrams (International Electrotechnical Commission) — The current official IEC graphical-symbol database and the electrotechnical areas it covers. Exact symbol identity data requires IEC access.; claim scope: standards
- IEEE/ANSI 315-1975 — Graphic Symbols for Electrical and Electronics Diagrams (IEEE Standards Association) — The official catalogue record for North American diagram symbols and reference-designation letters; IEEE lists the standard as inactive-reserved.; claim scope: standards, reference_designator
- IEC 61666:2010+AMD1:2021 — Identification of terminals within a system (International Electrotechnical Commission) — General principles for identifying terminals within systems; it does not replace the exact ordered-device datasheet.
- IEC 81346-2:2019 — Object classes and reference-designation codes (International Electrotechnical Commission) — The official classification scheme used to form reference designations across technical disciplines.; claim scope: reference_designator
- IEC 61082-1:2014 — Preparation of documents used in electrotechnology (International Electrotechnical Commission) — General presentation rules for electrotechnical diagrams, drawings, and tables.; claim scope: standards, usage
Geometry fingerprint: 925423f9d6ca0189. A changed SVG, canvas size, or terminal definition invalidates the recorded review.
Related symbols
- Contactor Coil symbol
- Contactor NO Contact symbol
- Timed Contact NC, Off-Delay (55-56) symbol
- Timed Contact NO, On-Delay (67-68) symbol
- Relay NO Contact symbol
- Time Delay Relay (Off-Delay) symbol
Physical breadboard, PCB, and panel mapping
No universal physical profile is published for this symbol yet. Create a versioned custom part from the exact manufacturer dimensions and terminal map before fabrication.
Place the Timed Contact NO, Off-Delay (67-68) symbol directly on a wiring diagram or schematic in the free online editor — no download required.