Timed Contact NC, On-Delay (55-56) Symbol

Timed Contact NC, On-Delay (55-56) schematic symbol
The Timed Contact NC, On-Delay (55-56) schematic symbol. Standard-specific details are listed below where available.

Definition: The on-delay NC timed contact is a normally closed contact operated by an on-delay timer: it opens only after the set time has elapsed from the moment the timer coil is energised, and it recloses immediately when the coil is de-energised.

Also known as: on-delay NC contact, TON NC contact, time-delayed break contact, delayed opening contact, NCTO contact, timer NC contact 55-56.

What the Timed Contact NC, On-Delay (55-56) symbol means

This symbol marks a circuit that stays made for a fixed time after the timer starts and is then broken. It is drawn closed (de-energised state), with the delay arc showing that the opening movement is the slow one.

How to identify the Timed Contact NC, On-Delay (55-56) symbol

Look for a normally closed (break) contact with the semicircular delay arc joined to the blade by a double line; the opening movement runs towards the centre of the arc. It carries the timer's tag and terminals such as 55-56, or 15-16 on a single-function timer relay.

Live editor identity: Live-library identity: `on-delay-contact-nc`, 40 × 60 canvas units, 2 logical terminals. Match this exact SVG and terminal list when identifying the placeable editor symbol; do not identify a physical package from the schematic outline alone.

Function and usage boundary

Energising the timer coil starts the delay; the contact stays closed until the delay ends, then opens and stays open while the coil remains energised. De-energising the coil recloses it at once.

Usage boundary: Use the Timed Contact NC, On-Delay (55-56) abstraction only when the intended circuit can be expressed through these logical ports: `in` (55), `out` (56). Select a versioned physical profile and exact manufacturer datasheet before assigning package pins, ratings, or fabrication dimensions.

Standards: IEC vs ANSI

IEC 60617IEC 60617 draws a timed contact as an ordinary make or break contact with the delayed-action mark (a small arc, the 'parachute') linked to the moving blade. Movement towards the centre of the arc is the delayed one, so the arc's orientation tells you whether the delay applies on operation (on-delay) or on release (off-delay). Terminal numbers follow EN 50005 practice: the function digit 5-6 marks a time-delayed break (NC) contact and 7-8 a time-delayed make (NO) contact, e.g. 55-56 and 67-68 on add-on timer blocks; single-function timer relays often use 15-16 (NC) and 15-18 (NO) for a timed changeover.
ANSI/IEEE 315ANSI/IEEE 315 and NEMA ICS practice draw the same function as a contact with an arrowed arc and the abbreviations TDC/TC (time delay closing) or TDO/TO (time delay opening), and label the contact with the timer's device tag (TR1, 2TR) rather than IEC function digits.
Key differenceBoth systems mark the delayed direction on the contact itself. IEC uses the parachute arc plus EN 50005 terminal digits (55-56, 67-68); North American drawings use NOTC/NCTO-style abbreviations and the TR device tag.

The displayed SVG is the live editor implementation, not a licensed reproduction or certification of an IEC or IEEE database glyph. Verify the exact official entry and project edition before issuing work.

Variant availability

Logical terminals

The live editor exposes `in` (55), `out` (56). These are stable logical terminal IDs for diagram connectivity, not a promise that they equal physical package pin numbers.

Logical IDEditor terminal name
in55
out56

Polarity and direction

This editor symbol does not encode a universal positive/negative orientation. Do not infer physical polarity or package pin numbering from left/right placement alone.

Reference designator

Project-defined: No single reference letter is asserted for this broad symbol. Apply the project standard and equipment-classification rules consistently.

Where the Timed Contact NC, On-Delay (55-56) symbol is used

Key facts

Common interpretation mistakes

Frequently asked questions

Why does a star-delta starter use both 55-56 and 67-68?

The on-delay NC (55-56) ends the star stage and the on-delay NO (67-68) starts the delta stage, both from the same timer, so the changeover happens at one set time. An interlock contact on each contactor still prevents both being closed together.

How is a timed contact linked to its timer?

By its device tag. The contact carries the same tag as the timer coil (for example KT1), and the cross-reference under the coil lists every contact it operates. In this editor the simulator links them the same way, so give the contact the timer's label.

What do 55-56 and 67-68 mean?

They are EN 50005 terminal numbers. The first digit is the contact's sequence number on the device; the second is the function digit, where 5-6 means a time-delayed break (NC) contact and 7-8 a time-delayed make (NO) contact. Ordinary instantaneous contacts use 1-2 (NC) and 3-4 (NO).

Sources and verification

Geometry fingerprint: 37b22316d46d2bcc. A changed SVG, canvas size, or terminal definition invalidates the recorded review.

Related symbols

Physical breadboard, PCB, and panel mapping

No universal physical profile is published for this symbol yet. Create a versioned custom part from the exact manufacturer dimensions and terminal map before fabrication.

Place the Timed Contact NC, On-Delay (55-56) symbol directly on a wiring diagram or schematic in the free online editor — no download required.